12 - MAIN OPTIONS
Options
Description
Advantages
Use for POWERCIAT LX
ST / HE / XE
Medium-temperature
brine solution
Implementation of new control algorithms and redesigned
evaporator to allow chilled brine solution production down
to -6°C when ethylene glycol is used (-3°C with
propylene glycol)
Covers specific applications such as ice storage and
industrial processes
●
Low-temperature brine
solution
Implementation of new control algorithms and redesigned
evaporator to allow chilled brine solution production down
to -12°C when ethylene glycol is used (-8°C with
propylene glycol)
Covers specific applications such as ice storage and
industrial processes
●
Light-brine solution,
down to -3°C
Implementation of new control algorithms to allow chilled
brine solution production down to -3°C when ethylene
glycol is used (0°C with propylene glycol)
Matches with most application requirements for ground-
sourced heat pumps and fits with many industrial processes
requirements
●
Unit equipped for air
discharge ducting
Fans equipped with discharge connection flanges -
maximum available pressure 60 Pa
Facilitates connections to the discharge ducts
●
Low Noise
Aesthetic and sound absorbing compressor enclosure
Noise level reduction
●
Xtra Low Noise
Acoustic compressor enclosure and low-speed fans
Noise emission reduction at reduced fan speed
●
Super Low Noise
Acoustic compressor enclosure, low-speed fans and
enhanced sound insulation of main noise sources
Noise level reduction for sensible site
ST / HE version, sizes
1308 to 4608
IP54 control box
Increased leak tightness of the unit
Protects the inside of the electrical box from dusts, water and
sand. In general this option is recommended for installations
in polluted environments
●
Tropicalisation of the
electrical box
Electrical box equipped with an electrical heater and a
fan. Electrical connections on the compressor painted
with a special varnish.
Allows safe operation in typical "tropical" climate. This option
is recommended for all applications where humidity inside the
electrical box can reach 80% at 40°C and unit can remain in
stand-by for a long time under these conditions.
●
Protection grilles
Metallic grilles on the 4 unit sides.
Improves protection against intrusion to the unit interior, and
protects the coil and piping against impacts.
●
Winter operation down
to -20°C
Fan speed control via frequency converter
Stable unit operation for air temperature down to -20°C
ST version, all sizes
230V electrical plug
230 V AC power supply source provided with plug socket
and transformer (180 VA, 0.8 A)
Permits connection of a laptop or an electrical device during
unit commissioning or servicing
●
Water exchanger frost
protection
Electric resistance heater on the water exchanger and
discharge valve
Water exchanger frost protection down to -20°C outside
temperature
●
Evaporator & hydraulic
module frost protection
Electric resistance heater on water exchanger, discharge
valve and hydraulic module
Water exchanger and hydraulic module frost protection down
to -20°C outside temperature
Sizes 808 to 1528
Total heat recovery
Unit equipped with additional heat exchanger in parallel
with the condenser coils.
Production of free hot-water simultaneously with chilled water
production
Sizes 808 to 3028
Evaporator with one
pass less
Evaporator with one pass on the water side. Evaporator
inlet and outlet on opposite sides.
Easy to install, depending on site. Reduced pressure drops
Sizes 808 to 3028
Master/slave operation
Unit equipped with supplementary water outlet
temperature sensor kit to be field installed allowing
master/slave operation of two units connected in parallel
Optimised operation of two units connected in parallel
operation with operating time equalisation
●
21 bar evaporator
Reinforced evaporator for extension of the maximum
water-side service pressure to 21 bar (standard 10 bar)
Covers applications with a high water column evaporator side
(typically high buildings)
●
Single power connection
point
Unit power connection via one main supply connection
Quick and easy installation
Sizes 3428 to 4608
Reversed evaporator
water connections
Evaporator with reversed water inlet/outlet
Easy installation on sites with specific requirements
●
Service valve set
Liquid line valve (evaporator inlet), compressor suction
and discharge line valves and economiser line valve
Allow isolation of various refrigerant circuit components for
simplified service and maintenance
●
Compressor discharge
valves
Shut-off valve on the compressor discharge piping
Simplified maintenance
●
Evaporator with one
pass more
Evaporator with one pass more on the water side
Optimise chiller operation when the chilled water circuit is
designed with low waterflows (high evaporator delta T)
●
Lon gateway
Bi-directional communication board complying with
Lon Talk protocol
Connects the unit by communication bus to a building
management system
●
HP single-pump
hydraulic module
Complete hydronic module equipped with water filter,
relief valve, one high pressure pump and drain valve.
For more details, refer to the dedicated chapter
(expansion tank not included; option with built-in
hydraulic safety components available).
Easy and fast installation (plug & play)
Sizes 808 to 1528
HP dual-pump hydraulic
module
Dual high pressure water pump, water filter, electronic
water flow control, pressure transducers. For more
details, refer to the dedicated chapter (expansion
tank not included; option with built-in safety hydraulic
components available)
Easy and fast installation (plug & play)
Sizes 808 to 1528
LP single-pump hydraulic
module
Single low-pressure water pump, water filter, electronic
water flow control, pressure transducers. For more
details, refer to the dedicated chapter (expansion
tank not included; option with built-in hydraulic safety
components available)
Easy and fast installation (plug & play)
Sizes 808 to 1528
LP dual-pump hydraulic
module
Dual low pressure water pump, water filter, electronic
water flow control, pressure transducers. For more
details, refer to the dedicated chapter (expansion
tank not included; option with built-in hydraulic safety
components available)
Easy and fast installation (plug & play)
Sizes 808 to 1528