Note:
Sulfuric acid and dry acid (sodium bisulfate) are not recommended for cell
cleaning. Under some conditions the electrolytic cell can be damaged.
WARNING
Read all cautions and directions provided with the muriatic acid used. Always add acid
to water. Use only with adequate ventilation. If strong odor is noticed, STOP, ventilation
is inadequate. Leave area immediately. If the work area is not well ventilated you MUST
use a properly fitted and maintained NIOSH approved respirator for acid fumes.
Prior to initiating the cell cleaning procedure, the acid wash assembly must be filled to the
25 gallon mark on the acid tank. Fill the tank with 20 gallons of water and then add 5
gallons of muriatic acid. It is important that 25 gallons of fluid is used. The cleaning
process will not work properly if less fluid is used.
Press NEXT to continue.
Fill to 25
gallon mark