4.3.
Mounting requirements
•
Make sure to always use sealant if installing in an outdoor environment or on
an uneven surface.
•
If possible, do not mount Charge Amps Halo in direct sunlight.
•
Do not install Charge Amps Halo in confined spaces.
•
Make sure the wall can support the product weight.
•
Recommended mounting height 750–1450 mm.
•
Use screws and plugs (
if required
) suitable for the wall material.
4.4.
Electric requirements
N.B. Local regulations might add additional requirements for the electrical installation.
•
Charge Amps Halo must be earthed through permanent electrical installation.
•
Only insert the electrical cable through the specified cable entry.
•
The cable ethernet connector must be of short type.
N.B Ethernet connection is only available for Charge Amps Halo OCPP version.
4.4.1.
Check the following before installation
•
The power is switched off at the main switch.
•
The incoming cabling is dimensioned to be able to connect the Charge Amps
Halo:
o
Minimum 2.5 mm
2
for 16 A
Electrical conditions in the facility and cable lengths may require a higher
cross-sectional area to meet the triggering conditions.
The selected cable’s outer diameter cannot exceed 14.0 mm.
o
Minimum 6 mm
2
for 32 A
Electrical conditions in the facility and cable lengths may require a higher
cross-sectional area to meet the triggering conditions.
The selected cable’s outer diameter cannot exceed 14.0 mm.
•
The product is properly fused:
o
1-phase 3.7 kW: 16 A, C or B Curve MCB*
o
3-phase 11 kW: 16 A, C or B Curve MCB*
o
1-phase 7.4 kW: 32 A, B Curve MCB*
These are minimum levels. Local regulations must always be fulfilled.
* MCB = Miniature Circuit Breaker, B Curve MCB’s trip at 3-5 times rated
current and C Curve MCB’s trip at 5-10 times rated current.