Make sure an RCD Type A is installed.
DC fault current protection is integrated into the charging station. An external
RCD type A is needed. Together, they have the same functionality as RCD type B
and replace the requirement of an RCD type B according to IEC 61851.
5.
Installation
1.
Switch off the power at the main switch.
2.
Make sure that the feed cable is isolated.
3.
Unpack Charge Amps Halo.
4.
Mount a separate type A RCD on the feed line to the Charge Amps Halo.
5.
Open the Charge Amps Halo with an Allen key H4.
Make sure that the O-rings securing the screws do not come loose.
6.
Remove all connected terminal blocks/connectors from the circuit board.
7.
Mount the external WiFi antenna (
some models only
).