D10.D15.DRS15-MANS
Apr ‘19
- 36 -
Fault
Code
1
Over-current.
Current too high in Motor Cable.
Check loading.
Check Motor.
Check Cables.
2
Over-voltage.
The DC link voltage has exceeded the limits.
- too short a deceleration time
Make deceleration time longer.
- high voltage spikes in supply
Check input voltage.
3
Ground Fault.
Insulation failure in Motor or wiring.
Check Motor wires and Motor.
8
System Fault.
- component failure
Reset the fault and restart the Unit.
- faulty operation
13
Frequency Converter under
Heatsink temperature is below -10°C.
temperature.
14
Frequency Converter over
Heatsink temperature is over 90°C.
Check the amount and flow of cooling air.
temperature.
Overtemperature warning is issued when the heatsink
Check the heatsink for dust.
temperature exceeds 85°C.
Check the ambient temperature.
Ensure the switching frequency is not too high
in relation to ambient temperature and motor
load
15
Motor stalled.
Motor stall protection has tripped.
Check Motor and load.
16
Motor over-temperature.
Motor is overloaded.
Decrease motor load.
17
Motor under-load.
Motor under-load temperature has tripped.
Check load.
22
EEPRON checksum fault.
Parameter save fault.
Should the fault re-occur, contact the Distributor.
- faulty operation.
- component failure.
25
Microprocessor watchdog
- faulty operation.
Reset the fault and restart the Unit.
fault.
- component failure.
Contact Distributor.
31
IGBT temperature
IGBT Inverter Bridge overtemp protection has detected too
Check loading.
(hardware).
high a short term overload current.
Check motor size.
Make identification run.
32
Fan cooling.
Cooling Fan of frequency converter does not start when
Contact Distributor.
ON command is given.
50
Analogue Input Iin < 4mA.
Current at the analogue input is less than 4 mA.
Check the current loop circuitry.
- control cable is broken or loose.
- signal source has failed.
52
Keypad communication
The data connection between the control keypad and the
Check keypad connection and possible keypad cable.
fault.
frequency converter is broken.
54
Slot fault.
Defective option board or slot.
Check board and slot.
Contact the nearest Vacon Distributor.
56
PT100 board temperature
Temperature limit values set for the PT100 board
Find the cause of temperature rise.
fault.
parameters have been exceeded.
Fault
Possible Causes:
Corrective Measures:
Variable Speed Drive (cont’d)
Common VSD Fault Codes
Noted below are the most common fault codes that may appear on the VSD. For a more thorough list, please
check the manual which deals exclusively with the Vacon Variable Speed Drive and which accompanied the Unit.