CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
Output & Relay Network Responses
The Fire relays and switched negative outputs in the panel will, by default, activate continuously for any
fire condition from the entire network.
The Fault relay and other switched negative outputs will also activate continuously, by default, if they have
been made programmable using programming option 4-1-4-2.
This option enables the default to be changed for each of the local relays and outputs. The response can
be either; CONTINUOUS, PULSING or NONE when a fire condition is received from any other panel in the
network.
Enter the above code and press the ENTER button.
The zone 1 fire LED will pulse indicating setting the response for the Fire
relay on the main PCB.
The relays and outputs are represented by zone LEDs 1 - 10 as per table
below.
Disable
Mode
Test
Mode
A pulsing red fire LED indicates which relay or output is selected and the setting is represented by the
amber fault LED. See tables below.
Use button 1 to move the pulsing fire LED to the required relay or output, then use button 2 to change the
response, indicated by the amber fault LED. Each press of button 2 will toggle through the 3 available
responses.
Test
Mode
Mute
Buzzer
Test
Lamps
Mute
Buzzer
Test
Lamps
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
Fire
Fault
Fire O/P Fault
OPA
OPB
Aux
OPA
OPB
Aux
Relay
Relay
(Main
O/P
Zone
Zone
Relay
Zone
Zone
Relay
(Main
(Main
PCB)
(Main
Ext. card Ext. card Zone
Ext. card Ext. card Zone
PCB)
PCB)
PCB)
1 (Zones 1 (Zones Ext. card 2 (Zones 2 (Zones Ext. card
5 - 8)
5 - 8)
1 (Zones 9 - 12)
9 - 12)
2 (Zones
5 - 8)
9 - 12)
Amber LED ON
Relay/output activates CONTINUOUSLY for other network panel fires
Amber LED PULSING
Relay/output PULSES for other network panel fires
Amber LED OFF
Relay/output NO RESPONSE for other network panel fires
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Note:-
The relay and output responses to a fire condition from their own panel are set using programming
option 4-2-4-2.
If a local response has been programmed, consideration should also be given to the network response
which may affect it.
ENTER
4
3
ENTER
4
3
2
2
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
4
2
2
4
RESOUND
SILENCE
RESET
1
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
Disable
Mode
1
2
Disable
Test
Mode
Mode