20
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
ZONE INTERFACE FUNCTION
This setting configures the last zone on the panel, (i.e. zone 2 on a 2 zone, zone 4 on a 4 zone, zone 6
on a 6 zone, zone 8 on an 8 zone and zone 12 on a 12 zone), to be used for interconnection from other
control panels.
It is possible, in the Level 3 engineering programming, to setup any zone for this function, however, this is
simply a shortcut method.
The function is enabled by setting switch 5 on the 7 Way DIL
switch located on the main PCB to the
‘ON’ position.
With switch 5 in the ‘ON’ position, the last zone becomes;
1.
Non-latching &
2.
Non-aux operating.
Note:
If the interface zone is also set to Twin Wire mode and sounders are connected to the zone circuit, the
following sounder operation will apply:
A fire
(470Ω)
signal to the interface zone will
NOT
operate the sounders connected to that Twin Wire circuit.
All other conventional (SNDR1 & SNDR2) and Twin Wire zone sounders will operate as normal.
A fire (470Ω) signal to any other zone will operate
ALL
conventional (SNDR1 & SNDR2) and Twin Wire
sounder circuits, including the sounders connected to the interface zone, as normal.
ON
1
2
3
4
5
6
7
Example connection
ZZONE2
ZONE2
ONE2
+ - + - + -
N
CCC
FIRE
FAULT
C NC NO