23
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
RESOUND
SILENCE
RESET
SETUP & PROGRAMMING
View History
The control panel stores a log of the last 40 events which have occurred. This is useful for identifying
intermittent faults or activations.
Enter the above code and press ENTER, the most recent event that has
occurred is displayed. Use the ENTER button to progress backwards
through the indications.
When the end of the log is reached the panel will drop out of view mode.
Disable
Mode
Test
Mode
During viewing it is possible to delete the entire history by pressing and
holding button 2. The panel will chirp to acknowledge deletion.
Mute
Buzzer
Test
Lamps
The panel will log and display the following events: zone fire activations, zone faults, power supply faults,
sounder circuit faults and repeater faults.
The last two (sounder circuit faults and repeater faults) have additional
information available which can be accessed by pressing and holding the
ENTER button continuously.
Sounder circuit faults
Disable
Mode
Test
Mode
If a sounder circuit fault is displayed, pressing and holding the ENTER button will reveal which sounder
circuit was at fault. This is indicated by the fire LEDs 1 - 6 as per the table below.
Zone 1 fire LED Zone 2 fire LED Zone 3 fire LED Zone 4 fire LED Zone 5 fire LED Zone 6 fire LED
Main PCB
SNDR 1
Main PCB
SNDR 2
Zone extension
card 1 (zones 5
- 8) SNDR A
Zone extension
card 1 (zones 5
- 8) SNDR B
Zone extension
card 2 (zones 9
- 12) SNDR A
Zone extension
card 2 (zones 9
- 12) SNDR B
Repeater faults
If a repeater fault is displayed, pressing and holding the ENTER button will reveal the following further
information.
The Repeater Fault LED indicates:
Slow Flash = faulty repeater, Normal Flash = repeater off line, Fast Flash = network cable error.
Red, fire LEDs 1 - 8 indicate which repeater was off line
Amber, fault LEDs 1 - 8 indicate which repeater had a PSU fault
When finished, enter the next programming code or disable the controls and return DIL switch 6 to ‘OFF’.
1
1
1
1
RESOUND
SILENCE
RESET
1
2
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
2
3
Mute
Buzzer
4
Test
Lamps
ENTER
RESOUND
SILENCE
RESET
1
2
Disable
Test
Mode
Mode
3
4
ENTER
Summary of Contents for CFX-Plus Pro-Sense 12
Page 72: ......