SETUP & PROGRAMMING
OPTION 11
. Inhibit Fire & Fault Buzzer on Network Slave Panel
It is possible to inhibit the fire and/or fault buzzers of the network slave panels. This is useful if the panels
are to be mounted together for a larger system. This option must be set on each individual slave panel.
With the zone 11 fire LED lit press the ENTER button. The zone 1 fire LED will pulse to indicate editing the
panels fault buzzer.
Editing of the fault buzzer is indicated by the zone 1 LEDs and editing the panels fire buzzer is indicated
by the zone 2 LEDs.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fire LED to the required zone as per
above.
Then use button 2 to Disable or Activate the buzzer indicated by the amber fault LED.
Fault LED OFF = Buzzer Active
~
Fault LED ON = Buzzer Disabled
When finished press the ENTER button again and the zone 11 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
When finished all panel wide programming, enter the next programming code or disable the controls and
return DIL switch 2 to ‘OFF’.