26
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
OPTION 2.
Set Number of Repeater Panels on System
If repeater panels are to be used, the quantity on the system, 1- 8, must be set up for monitoring purposes.
An incorrect quantity will cause a repeater fault to be shown on the panel.
With the zone 2 fire LED lit, the amber, fault LEDs will show the current quantity of repeaters set 0 - 8. (1
LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 2 fire LED
will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Disable
Mode
Test
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPTION 3.
Set Time For Panel Delay Timer
The panel delay time for all outputs is set here. To actually apply the delay to the desired outputs, see
programming code 2-3-2-3. The default setting is 3 minutes but can be changed to between 1 - 10
minutes.
With the zone 3 fire LED lit, the amber, fault LEDs will show the current time set. The time is represented
by a binary code using LEDs 1 - 4.
LED 1 = 1min, LED 2 = 2min, LED 3 = 4min, LED 4 = 8min. Therefore if LEDs 1 & 2 are lit the time is 3
minutes (1 + 2). If LEDs 2 & 4 are lit the time = 10 minutes (2 + 8).
Press the ENTER button, zone 3 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the time, each press will increase or decrease the time by
1 minute. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 3 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Disable
Mode
Test
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
ENTER
4
3
2
2
1
ENTER
4
3
2
2
1
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
3
Mute
Buzzer
4
Test
Lamps
ENTER
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
Disable
Mode
1
Disable
Mode