CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
A series of programmable engineering options are available. These
programming modes are initiated by entering a four-digit code using
buttons 1 - 4 on the keypad followed by the ENTER button.
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
To access Level 3 options, first set switch 6 on the 7 Way DIL switch located on the main PCB to the
‘ON’
position. Then activate the controls by turning the key switch or by entering the four-digit code (see
Activate Controls in the OPERATING section).
Once the controls are active, the ‘Access Level’ indicator will pulse to signify that Level 3 access is active.
Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options
to set and the fault LEDs indicate the status of these settings.
Generally button 1 is used to scroll the indications (button 3 can also be used to scroll backwards).
Pressing and holding button 1 for 3 seconds at any time will exit the programming mode completely.
N.B.
The panel will automatically save settings & drop out of programming modes if left idle for more than
approximately 30 seconds.
It is possible to review the settings within a programming mode without changing them. Steady Fire LEDs
indicate review mode. To edit a setting first use button 1 to select the required option, pressing ENTER
enables editing of the option. Flashing fire LEDs indicates edit mode and button 2 is used to change the
setting.
Pressing ENTER again will exit ‘edit’ mode back to ‘review’ mode.
Some programming modes are denoted with (EN54!). Where this symbol appears EN54 compliance may
be affected by this setting.
ENTER
4
3
2
1
+ -
RESOUND
SILENCE
RESET
ZONE1
ON
1 2 3 4 5 6 7
ON
1 2 3 4 5 6 7
ON
3 4 5 6 7
ZONE4
+ -
E3
-
ZON
+
ZONE2
+ -