CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
ZONE B - Set to Fire Pump Indication
The second zone will confirm that the pump has started to run due to demand for fire extinguishing water:
Pump idle;
•
i.e. 4K7 EOL resistor only. No indication at all (normal)
Pump running;
•
3K9, Zone fire LED comes on and panel buzzer sounds intermittently, the general fire alarm and
alarm bells do NOT operate and the alarm is non-latching.
Pump fail to run;
•
470 Ohm, Zone fault LED on and panel buzzer sounds continuously but with the general fire and
sounder circuits inhibited and the alarm / fault conditions are no latching.
Select zone(s) to be programmed for Gate Valve or Fire Pump status monitoring as per ‘Zone Function
Settings’ programming mode 3
-1-2-1.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fire zone 1 LED will now pulse to indicate the editing of attribute 1 (fire latching) for the selected zone.
Use button 1 to scroll to pulsing fire LED 8 (gate valve & fire pump indications).
Then use button 2 to set the status required for that zone, indicated by the amber, fault LED.
OFF = normal zone
ON = Gate Valve Status Indication
PULSING = Fire Pump Status Monitoring
Test
Mode
Mute
Buzzer
Test
Lamps
Mute
Buzzer
Test
Lamps
Press the ENTER button to return back to the zone selection, indicated by a steady zone fire LED
When finished all the zone function programming, enter the next programming code or disable the controls
and return DIL switch 2 to
‘OFF’.