CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
OPTION 4.
Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)
The battery monitoring may be disabled for applications where this is appropriate such as non fire alarm
use or where no battery backup is required.
Note: There is no remote PSU fault input available on the
panel.
With the zone 4 fire LED lit, the amber, fault LEDs will show the current setting.
LED 1 OFF = monitored batteries (default).
LED 1 ON = batteries un-monitored.
LED 2 OFF = no Hi Z monitoring
LED 2 ON = battery Hi Z monitored (default)
Press the ENTER button, zone 1 fire LED will pulse to indicate ‘edit mode’ for std battery monitoring.
Use button 1 to toggle between pulsing fire LEDs 1 & 2 for editing std or Hi Z battery monitoring as per
above.
Now use button 2 to change the setting indicated by the amber fault LED as per above.
When finished press the ENTER button again and the zone 4 fire LED will return to steady
‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Disable
Mode
Test
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPTION 5.
Setup Internal PCB Configuration
The control panel monitors all internal PCBs for correct function. If adding or removing any of the additional
extension zone cards, the panel must be programmed for the new configuration.
With the zone 5 fire LED lit, the amber, fault LEDs will show the current configuration setting. Each of the
2 possible additional zone cards are represented by LEDs 1 - 2 as per table below.
LED 1 (ON)
LED 2 (ON)
Extension zone card 1
(zones 5 - 8)
Extension zone card 2
(zones 9 - 12)
Press the ENTER button, zone 1 fire LED will pulse to indicate editing of 1st additional PCB as per table
above. Use button 1 to move to the fire LED for the relevant PCB as per table.
Now use button 2 to change the setting indicated by the amber fault LED (LED ON = PCB included, OFF
= not included).
When finished press the ENTER button again and the zone 5 fire LED will return to steady ‘view mode’,
with the amber, fault LEDs showing the new configuration.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
ENTER
4
3
2
2
1
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
Disable
Mode