REVO C
2PH from 60A to 800A - 690V
User’s manual
49
Parameter Name
Description
Default
Range
Modbus
Address
Par.
Type
Rtx Scale
Set the value of retransmitted
parameter to be represented by
the full scale of the analog output.
See the table below
0
0 to 9999
124
Read
Write
Retransmit
Recommended
Retransmission
Scaling
Resulting Signal
(4 to 20 mADC)
Resulting Signal
(0 to 20 mADC)
Resulting Signal
(0 to 10 VDC)
Max Value
Set Point
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100.0
V Output
xV
where
x
is the
Nominal Line
Voltage
4mADC = 0V
20mADC = xV
0mADC = 0V
20mADC = xV
0VDC = 0V
10VDC = xV
999.9
I Output
xA
where
x
is the
Nominal Line
Current
4mADC = 0A
20mADC = xA
0mADC = 0A
20mADC = xA
0VDC = 0A
10VDC = xA
999.9
Power
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Rtx Type
Choose type of signal for the retransmission output
1
69
Read
Write
Option
Value
4-20mA
0
0-10V
1
0-20mA
2
DEFAULT:
0-10V
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Start Disp
Choose which parameter is displayed on the home
page at power-up
1
60
Read
Write
Option
Value
Current
0
Volts Out
1
Power
2
DEFAULT:
Voltage
1
Summary of Contents for REVO C 2PH 690V
Page 2: ......