REVO C
2PH from 60A to 800A - 690V
User’s manual
25
8.3 Cable dimensions (suggested) of Earth and of the Command Terminals
Current
Earth
Command Terminals
Cable
Screw
Cable
mm²
AWG
M
mm²
AWG
60A (S11)
16
6
M8
0,50
18
90A (S11)
16
6
M8
0,50
18
120A (S13)
16
6
M8
0,50
18
150A (S13)
25
4
M8
0,50
18
180A (S13)
25
4
M8
0,50
18
210A (S13)
25
4
M8
0,50
18
300A (S14)
50
1
M8
0,50
18
400A (S14)
50
1
M8
0,50
18
450A (S14)
70
1/0
M8
0,50
18
500A (S14)
70
1/0
M8
0,50
18
600A (S14)
70
1/0
M8
0,50
18
700A (S14)
70
1/0
M8
0,50
18
800A (S16)
70
1/0
M8
0,50
18
Bus bar
2PH 300A 2PH 400A 2PH 450-800A
M10
30
15
15
14
M10
66
33
33
12
M10
M10
66
36
15
15
15.5
Summary of Contents for REVO C 2PH 690V
Page 2: ......