10.5.8 To reset the power totals:
1) Click
Test
, if not already on the test view
2) Click
Online
3) Click
Reset Totals
4) Click
Yes
10.5.9 Setting Up and Using Data Logging
To set up data logging:
1) Click
Test
, if not already on the test view
2) Click
Online
3) Click
Load Analyzer
4) On the
Load Analyzer
view click
Data
Log
5) In the
Data Log
window ensure the
slider is set to
Log Enabled
6) Click
Set Time
7) If necessary Set the date and time and
close the date/time window
8) Set
Log Time
to the number of seconds
between records
9) Click
Connect
10) Click
Confi g
11) Click
Load Confi guration
to view the
current list of logged parameters
12) For up to ten parameters to log:
-Click
+
to add a parameter to the list
-In a row in the list either: Type a parameter’s Modbus address in the
Par
fi eld
OR
-Select the parameter from the drop down list in the
Name
fi eld
13) Click
Write Confi guration
to send the parameter list to the controller
14) Click
Close
15) Click
Disconnect
16) Close the
Data Log
window