REVO C
2PH from 60A to 800A - 690V
User’s manual
51
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
WD Reset
Set the amount of time to wait for
a communication message before
triggering the watchdog error
5
0 to 255
Sec
143
Read
Write
Wi-Fi Addr
Indicate the IP address of the WiFi
connection in the power controller
0 to 255
94-95
96-97
Read
Only
Field Name
Only with Profinet option
0 to 255
79-80
81-82
Read
Only
Unit Name
Indicate the name of the unit
max 16
characters
83-84
85-86
87-88
89-90
Read
Only
Port 2 Addr
Set the address for the secondary serial
port or the Profibus Address
0
0 to 1024
122
Read
Write
Port 2
Indicates the type of secondary
communication port
119
Read
Write
Option
Description
Value
Disabled
No secondary communication port
0
Ethernet
Modbus TCP or ProfiNet
1
RS-485
RS-485
2
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Wi-Fi
Enable or disable WiFi communication
0
120
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0
Caution:
If Bus port is not connected or in error, all writable parameters are set to
0
value