4.4.1. Electricity supply
The connection is to the two connection terminals and the earth bar. The MeteoR2 must have a 230V
single phased 50Hz power supply protected by a 30mA ground fault protection, which supplies
sufficient intensity. There must also be a short-circuit protection (max. 16A) on the control box
power supply line. The power supply cable size must be suitable and adapted to the total length and
the elements connected to the MeteoR2 .
The control box includes a protection device for the filtration pump which mon-
itors the power consumed, but it does not include short-circuit protection or
differential protection devices. It is essential to ensure that the correct protec-
tive systems are installed upstream of the cabinet!
Control box ref. PF10Y002 is perfectly suited to guarantee the electric protection for the MeteoR2
and the equipment connected to it.
Use the earth bar at the bottom of the control box to connect it.