3.2. Filtering management
It is possible for the MeteoR2 to calculate ideal filtering time every day (AUTO mode) by simply
choosing the start-up time. If you prefer to control the pump operating times, it is also possible (in
PROG mode) to programme 3 fixed filtering time slots (= clock).
3.2.1. Pump current monitoring
The MeteoR2 has a built-in current consumption measurement system for the pump (or pumps if
there is a booster pump). There are several monitoring options available:
• No current monitoring
• Low intensity monitoring ( I < 0.75 In for 2 minutes) only (unpriming, running with no water, etc.)
• Over-intensity monitoring ( I > 1.25 In for 2 minutes) only (shaft jammed, etc.)
• Full monitoring (low and high intensity)
The pump is calibrated automatically and managed by the MeteoR2. In this way, a single control
box model can be used to protect different pump powers without having to change circuit-breaker
calibres. The pump's power consumption must be between 0.3 and 12A.