Fast track service manual for FA-20:

   

 

         

            

 

 

1. Control of electricity supply and internal power supplies:  
 

If 230Vac is connected to the FA-20, then you should (within 3 seconds after power on) be 
able to se the 3 LED’s in “traffic light” formation (red, yellow, green) inside the FA-20 light 
up just to the right of the middle. These 3 LED’s indicates 3 internal voltages 24V, 3.3V and 
12V. All 3 LED should all light up constantly. If this is not the case, you will have to check 
that  there  are  230Vac  on  the  terminals  and  if  this  is  not  the  case  you  have  to  check  the 
fuse under plastic lid to the right of the connection terminals. The fuse will blow in case of 
lightning  and  other  similar  influences  –  and  will  in  some  cases  protect  the  FA-20  against 
further damage. If normal function cannot be obtained by change of fuse – then the FA-20 
should be taken down and sent to service. 
  

2. Control of the GSM connection: 

 

The  little  green  interior  LED  to  the  right  of  the  key  is  controlled  only  by  the  GSM/GPRS 
modem and tells about the GSM-modems condition: 

  
   

1. Always OFF: 

 

Power error or hit by a bug. 

   

2. 

One flash per second:

 

Modem is looking for network  

      

                            

 

Modem is about to turn off / reboot 

   

 

 

Modem has a defect/ no SIM-card  

   

 

 

(PIN-code active on the SIM-card?) 

   

3. Always ON: 

 

GSM/GPRS communication is ongoing.  

   

4. One flash per 3 sec.: 

GSM-modem  is  on  the  GSM-network  and 
ready. 

 

If there is no power error like in point 1 and the little green internal LED is turned off, then it 
is properly an error in the GSM modem and the FA-20 should be taken down and sent to 
service. If the little green internal LED on the other hand flashes once per second, then it is 
probably  a  local  problem  in  form  of  a  lack  of  GSM  coverage,  defective  antenna  or  SIM-
card, SIM-card with PIN-code on or missing payment. Try with another tested SIM-card or 
a different telephone operator or try a wired antenna instead of whip. 

 

Test  the  communication  by  sending  the  FA-20  a  regular  text  SMS  containing  NNNN 
(NNNN  is  the  default  password  –  can  be  changed  by  the  main  station)  from  a  regular 
cellular phone. If the FA-20 receives the SMS the FA-20 will answer  with a service SMS, 
among others containing measured field strength. The field strength should be between –
50dBm (good signal) and –90dBm (weak signal – but typical still usable). By signal weaker 
then –90dBm a different mounting place of FA-20 should be considered.  

 

3. Controlling the FA-20 computers operating mode: 
 

If there is no power error, then you can see the FA-20’s computer operation mode on the 
big red and the big green LED at the top to the left (visible through the lid). If the red LED is 
constantly on and the green LED is constantly off then there is a permanent error condition 
and the FA-20 should be dismantled and sent to service. All other conditions of the green 
LED and the red LED is described on page 19 in the installation guide and will normally not 
mean a need for service. 

 

 

Summary of Contents for FA-20

Page 1: ...RS SMS based remote metering 1 FA 20 in brief 2 Product information 3 Installation Instructions Rev 2013 02 01 CB Svendsen A S Kirke Vaerloesevej 22 24 DK 3500 Vaerloese Denmark Phone 45 4448 5286 Fax...

Page 2: ...lses can be freely mixed FA 20 is delivered preprogrammed with a number of serial meter drivers supporting different serial manufacturer protocols Changing between the drivers is easily done trough SM...

Page 3: ...3 FA 20 Product information...

Page 4: ...is exceeded these conditions will be transmitted to the main station through an extraordinary data communication programmable Furthermore the FA 20 saves 3 sets of serial readings The latest reading...

Page 5: ...o of days 24 h 1h logging 31 27 24 22 20 18 The FA 20 is remotely programmed from the main station logging parameters set up and selection of buffers to which data is logged Logging of pulses and seri...

Page 6: ...a random number of minutes within a time window which is programmable from the IT centre FA 20 also supports dial back at absolute time where it is the main station who chooses the time including date...

Page 7: ...can preserve its content Log data and for example the latest monthly reading is always stored in the F RAM which does not need a battery to preserve its memory FA 20 features a special integrated cir...

Page 8: ...4 band GSM module Temperature range 20 to 45 Relative humidity 15 to 95 not condensing Density class IP54 Dimensions 105 x 180 x 50 mm W x H x D without antenna Remember 30 mm clearance for cable entr...

Page 9: ...ultical 801 via data module an without compatability module KM6 data module is mounted internally in 801 8 Div Multical with M bus module mounted internally in Multical Max M bus 9 Unigas 61E via data...

Page 10: ...10 FA M2000 GSM main station modem...

Page 11: ...s ready for use and special settings of parameters can be installed and stored permanently in the GSM modems memory FA M2000 supports V 110 data communications which allow data to be transferred at sp...

Page 12: ...12 Installation guide FA 20...

Page 13: ...n the lid is pulled downwards until it locks 2 The physical location of FA 20 Typically FA 20 is placed next to one of the meters that are to be logged The most convenient location is against a wall v...

Page 14: ...y sending FA 20 a SMS FA 20 with firmware 1 30 or later contains as minimum the following software drivers KMX handles various Multical with 3 wire data module i e Multical III 66C Compact 401 and 601...

Page 15: ...to terminal 10 in FA 20 Brown wire Reg pin 5 in Unigas is connected to terminal 11 in FA 20 It is recommended to connect FA 20 directly to the internal plug in Unigas and let the plug with the RPG co...

Page 16: ...with M bus L G WSD and WSF L G 2WR4 2WR5 and UH50 with G2 or G4 Sensus Mechanical water meter with M bus Hydrometer Sharkey with M bus and Infocal 5 with M bus ABB Type Delta with M bus Use Fa 20 conn...

Page 17: ...n communication with the GSM GPRS modem the big red LED Top right corner visible through the lid will after a few seconds flash quickly and stable to indicate errors Common log operation is stopped 9...

Page 18: ...will light constantly during the communication and in case of error the red LED will report the error by a 3 second long flash Note Automatic readout after power up Approximately 2 3 min after power...

Page 19: ...ed LED is ON for 3 sec Failure without any permanent influence on normal operation 1 A serial reading of a meter failed 2 Data communication with the main station failed 3 Brief power failure More aty...

Page 20: ...If there is no power error like in point 1 and the little green internal LED is turned off then it is properly an error in the GSM modem and the FA 20 should be taken down and sent to service If the...

Page 21: ...eadout from serial meters then you can test the communication between the FA 20 and serial meters by pushing the key After a keystroke the big green LED will flash once briefly per second by readout o...

Page 22: ...002000 Pulse counter stand for pulse input no 2 In 1 OFF 2 OFF Signal on digital input no 1 on off and no 2 on off In 3 OFF 4 OFF Signal on digital input no 3 on off and no 4 on off Out 1 OFF 2 OFF Re...

Page 23: ...nd for M1 Volume 839 Volume counter stand for M1 Mbus2 90012312 Serial no read from meter connected to M2 Energy 3552 25 Energy counter stand for M2 Volume 88243 88 Volume counter stand for M2 Multi 3...

Page 24: ...variants Above is the fully wired version with 4 pulses or digital S01 inputs 2 relay outputs and 2 x 0 4 20 mA inputs Below is a variant only with 4 pulses or digital inputs Relay outputs Max 27Vdc...

Page 25: ...Ds in the middle column shows pulses from pulse input 5 to 8 and the orange LEDs in the right column shows pulse inp Pulse input 9 to 12 in connector In the middle to the right NOTE Pulse input 1 and...

Page 26: ...cates the current status of the output Light in the LED means output is active closed loop Specification These are 2 electrically isolated optocoupler outputs Max applied voltage is 27Vdc open loop Ma...

Reviews: