16
6. Connection of serial meter to M-bus port M1 or M2:
Meter interface ports M1 and M2 are the classic M-bus ports that are operated via the
multifunction driver "MAX M-Bus". MAX M-bus itself recognizes the type of M-bus meter
accessing and searching even after relevant properties - including the legal meter serial
number and customer number (usually equal to the meter serial number).
The same driver “MAX M-bus” is also available for "Multi". Multi-port can -
in addition to
supporting the M-bus-based targets -
also
support a wide range of manufacturer-defined
serial interface and protocols, when the correct software driver is selected via a text SMS to
the FA-20.
Connecting the following meters with M-bus to ”M1” or M2
AquaMetro : AquaMetro with M-bus.
Brunata HG : HGR, HGP, HGQ and HG754.
Elster
: Mechanical gas meter with M-bus
Kamstrup : Multical III / 66C with M-bus.
Multical 401 / 601 / 801 with M-bus.
(NB.: it is cheaper to use data base for Multical than M-bus module).
Kamstrup
: All types of Power and water meters with M-bus.
L&G
: WSD and WSF.
L+G
: 2WR4, 2WR5 and UH50 with G2 or G4
Sensus
: Mechanical water meter with M-bus.
Hydrometer : Sharkey with M-bus and Infocal 5 with M-bus.
ABB
: Type “Delta” with M-bus.
Use Fa-20 connection terminals 5+6 for port M1 or terminals 7+8 for port M2.
7. Connecting 230 VAC:
FA-20 comes in a 230 VAC version.
FA-20 should under no circumstance be connected
to other voltages!
FA-20 contains 2 connectors for 230 VAC, which are placed at the bottom to the right. There
shall be used double isolated cables approved for 230Vac for example 2x0,75 mm2. The
phase used for FA-20 should be secured with a 10A fuse or less. The cord to the electricity
supply must have an outer diameter of 6mm ± 1mm for the sake of optimum strain relief and
mounted via the PG-clamp.
All installation must be done be authorized electrician and in agreement with national and EU
legal installation instructions. This product must only be used in EU.
8. Admissions of phone numbers into FA-20:
Admissions of phone numbers into FA-20 are done through the IT software centre. The IT
software calls the FA-20 up using GSM/GPRS communication, and encodes the telephone
number and possible IP related information into the FA-20.