24
Option module type ”+4 pulse” and ”+4 pulse+2analog inputs”
Both the equipped variants.
NOTE: SW1 must always be
OFF (on both variants):
Above is the fully wired
version with 4 pulses or digital
(S01) inputs, 2 relay outputs
and 2 x 0(4)-20 mA inputs.
Below is a variant only with 4
pulses or digital inputs.
Relay outputs:
Max. 27Vdc or 20Vac.
Max/min: 100mA / 0,5mA.
If the relay is to operate en
external relay:
Max. 24Vdc/20mA and a
freewheeling diode is required.