background image

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS

PROCEDURE

Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will pre-
vent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.

1. Disconnect all power to the furnace. DO NOT TOUCH THE

CONTROL OR ANY WIRE CONNECTED TO THE CON-
TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC-
TROSTATIC CHARGE TO GROUND.

2. Firmly touch a clean, unpainted, metal surface of the furnace

chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.

3. After touching the chassis you may proceed to service the

control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).

4. If you touch ungrounded objects (recharge your body with

static electricity), firmly touch furnace again before touching
control or wires.

5. Use this procedure for installed and uninstalled (ungrounded)

furnaces.

6. Before removing a new control from its container, discharge

your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the furnace. Put all used AND
new controls into containers before touching ungrounded
objects.

7. An ESD service kit (available from commercial sources) may

also be used to prevent ESD damage.

Table 1—Dimensions (In.)

UNIT SIZE

A

D

E

VENT CONN

SHIP. WT (LB)

070-08

14-3/16

12-9/16

12-11/16

4

123

070-12

14-3/16

12-9/16

12-11/16

4

126

091-14

17-1/2

15-7/8

16

4

142

111-16

21

19-3/8

19-1/2

4

165

136-20

24-1/2

22-7/8

23

5

188

155-20

24-1/2

22-7/8

23

5

196

Fig. 1—Dimensional Drawing

A00210

A

D

13

16

E

11

16

11

16

28 

1

2

39 

7

8

24 

5

16

11

16

3

1

16

1

12 

5

16

3

8

13

16

3

8

AIR INLET

7

8

-IN. DIA HOLE

POWER ENTRY

7

8

-IN. DIA

ACCESSORY

3

4

-IN.

 

DIA HOLE

GAS ENTRY

1

2

-IN. DIA HOLE

THERMOSTAT

WIRE ENTRY

SIDE INLET

VENT CONN

1.  Two additional 

7

8

-in. dia holes are located in the top plate.

2.  Minimum return-air openings at furnace, based on metal duct.  If flex duct is used,
     see flex duct manufacturer's recommendations for equivalent diameters.
     a.  For 800 CFM–16-in. round or 14

1

2

 x 12-in. rectangle.

     b.  For 1200 CFM–20-in. round or 14

1

2

 x 19

1

2

-in. rectangle.

     c.  For 1600 CFM–22-in. round or 14

1

2

 x 23

1

4

-in. rectangle.

     d.  For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific
          use of single side inlets.  The use of both side inlets, a combination of 1 side and the bottom, or the
          bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.

NOTES:

3

8

13

16

3

8

11

16

1

1

16

19

13

16

7

8

-IN. DIA

POWER ENTRY

AIRFLOW

OUTLET

1

2

-IN.

 

DIA

R.H. GAS ENTRY

7

8

-IN. DIA ACCESSORY

1

2

-IN. DIA THERMOSTAT

WIRE ENTRY

SIDE INLET

14

1

2

1

23

1

4

SIDE RETURN

DUCT LOCATION

1

1

4

TYP 1

5

8

TYP

2

Summary of Contents for WeatherMaker 8000 58YAV

Page 1: ...he unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the...

Page 2: ...ough 5 before bringing the control or yourself into contact with the furnace Put all used AND new controls into containers before touching ungrounded objects 7 An ESD service kit available from commer...

Page 3: ...changing residential construction practices We require these instructions as a minimum for a safe installation Application of this furnace should be indoors with special attention given to vent sizin...

Page 4: ...allel with or on the downstream side of the unit to avoid condensation in the heat exchangers When installed parallel with a furnace dampers or other means used to control the flow of air must prevent...

Page 5: ...ch they connect The minimum dimension of ducts must not be less than 3 in See Fig 4 AIR DUCTS Step 1 General Requirements The duct system should be designed and sized according to accepted national st...

Page 6: ...HROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Minimum of...

Page 7: ...lt should not exceed 1 1 2 in 1 Lay furnace on its back Locate and drill 5 16 in diameter hole in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole...

Page 8: ...shutoff valve Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached If the furnace has been attached it is recommended tha...

Page 9: ...use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic Air Cleaner EAC Two quick connect terminals marked EAC 1 and EAC 2 are provided for EAC connection See Fig 10 These terminals are ener...

Page 10: ...polarity must be maintained for correct operation Thermostat wire connections at R W COM 24V and Y must be made at the 24 v terminal block on the control board The gas service pressure must not exceed...

Page 11: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOT...

Page 12: ...reverts to continuous operation after the heating cycle is completed When the thermostat calls for cooling the blower operates on cooling speed When the thermostat is satisfied the blower operates on...

Page 13: ...cteristics b Adjust manifold pressure to obtain input rate 1 Remove regulator adjustment seal cap See Fig 12 2 Turn adjusting screw counterclockwise out to de crease manifold pressure or clockwise in...

Page 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Page 15: ...0 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2 3...

Page 16: ...U S A Only 575 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 600 43 2 5 43 2 6 43 2 7 43 2 7 43 2 8 9001 625 43 2 3 43 2 4 43 2 4 43 2 5 43 2 6 650 43 2 1 43 2 2 43 2 3 43 2 3 43 2 4 to 675 48 3 7 43 2 0 43 2 1...

Page 17: ...dually block off the return air after the furnace has been operating for a period of at least 5 minutes As soon as the limit has shut off the burners the return air opening should be unblocked By usin...

Page 18: ...us code 31 If hot surface igniter glows when inducer motor is disconnected shut down furnace immediately Determine reason pressure switch did not function properly and correct condition e Turn off 115...

Page 19: ...d Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate ____________ Temperature Rise A...

Page 20: ...Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog...

Reviews: