background image

INTRODUCTION

The Model 58YAV, Series A Furnace is available in sizes 66,000
through 154,000 Btuh input capacities.

The design of the upflow gas-fired furnace is CSA (A.G.A. and
C.G.A.) certified for natural and propane gas and for installation
on combustible flooring, in alcoves, attics, basements, closets, or
utility rooms. The furnace is factory-shipped for use with natural
gas. A factory accessory gas conversion kit, as listed on the
furnace rating plate is required to convert furnace for use with
propane gas. The design of this furnace line is not CSA (A.G.A.
and C.G.A.) certified for installation in mobile homes, recreation
vehicles, or outdoors.

Before installing the furnace in the United States, refer to the
current edition of the NFGC and the NFPA 90B. For copies of the
NFGC and NFPA 90B, contact the National Fire Protection
Association Inc., Batterymarch Park, Quincy, MA 02269; or for
only the NFGC contact the American Gas Association, 400 N.
Capitol St., NW, Washington DC 20001.

Before installing the furnace in Canada, refer to the NSCNGPIC.
For a copy of the NSCNGPIC, contact Standard Sales, CSA
International, 178 Rexdale Boulevard, Etobicoke (Toronto), On-
tario, M9W 1R3, Canada.

Installation must comply with regulations of serving gas supplier
and local building, heating, plumbing or other codes in effect in the
area in which installation is made. In absence of local building
codes, installation must comply with NFGC in the United States
and the NSCNGPIC and all authorities having jurisdiction in
Canada.

These instructions cover minimum requirements for a safe instal-
lation and conform to existing national standards and safety codes.
In some instances, these instructions exceed certain local codes
and ordinances, especially those that may not have kept pace with
changing residential construction practices. We require these
instructions as a minimum for a safe installation.

Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, and unit sizing. Improper installation or
misapplication of the furnace can require excessive servicing
or cause premature component failure.

This furnace is designed for a minimum continuous return-air
temperature of 60°F db or an intermittent operation down to 55°F
db such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F db.

Fig. 2—Clearances to Combustibles

A00299

For furnaces wider than 14.25 inches (362mm) may be 0 inches.
For single wall vent  6 inches. For Type B-1 vent  3 inches.

3

256

87

-1

01

 R

E

V

. A

 (

lit

)

#

This forced  air  furnace is equipped  for  use  with natural gas at

altitudes 0-10,000 ft (0-3,050m).

An accessory kit,  supplied by  the  manufacturer,shall be used  to

convert to propane gas use or may be required for some natural gas
applications.

This furnace is for  indoor installation in a building constructed  on

site.

This furnace may  be installed on combustible flooring in alcove or

closet at minimum clearance from combustible material.

This furnace may be used with a Type B-1 Vent and may be vented

in common with other gas-fired appliances.

Clearance in inches

BO

T

T

O

M

  1" #

0"

1"

1"

30"

MIN

S I

DE

F R

ON

T

B

C K

A

S E

R VI

E

C

FR

ON

T

S I

E

U

F

RN

AC

E

#

T

O

P /

 PL

E

N

U

M

D

##

##

INSTALLATION WITH CHIMNEY ADAPTER KIT

This furnace is approved for UPFLOW installations only.

Vent Clearance to combustibles:

   For Single Wall vents 6 inches.
   For Type B-1 vent  1 inch .

MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION

0"

Chimney Adapter  Kit No. KGACA01014FC or No. KGACA01015FC may
be  required  for  some  exterior  masonry  chimney  applications.  See
Installation Instructions, Single-Stage Vent Tables For Category I
Fan-Assisted Furnaces.

A99075

FRONT

RETURN
AIR

MAX 85

°

F

MIN 55

°

F

°

F

°

F

3

Summary of Contents for WeatherMaker 8000 58YAV

Page 1: ...he unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the...

Page 2: ...ough 5 before bringing the control or yourself into contact with the furnace Put all used AND new controls into containers before touching ungrounded objects 7 An ESD service kit available from commer...

Page 3: ...changing residential construction practices We require these instructions as a minimum for a safe installation Application of this furnace should be indoors with special attention given to vent sizin...

Page 4: ...allel with or on the downstream side of the unit to avoid condensation in the heat exchangers When installed parallel with a furnace dampers or other means used to control the flow of air must prevent...

Page 5: ...ch they connect The minimum dimension of ducts must not be less than 3 in See Fig 4 AIR DUCTS Step 1 General Requirements The duct system should be designed and sized according to accepted national st...

Page 6: ...HROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Minimum of...

Page 7: ...lt should not exceed 1 1 2 in 1 Lay furnace on its back Locate and drill 5 16 in diameter hole in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole...

Page 8: ...shutoff valve Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached If the furnace has been attached it is recommended tha...

Page 9: ...use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic Air Cleaner EAC Two quick connect terminals marked EAC 1 and EAC 2 are provided for EAC connection See Fig 10 These terminals are ener...

Page 10: ...polarity must be maintained for correct operation Thermostat wire connections at R W COM 24V and Y must be made at the 24 v terminal block on the control board The gas service pressure must not exceed...

Page 11: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOT...

Page 12: ...reverts to continuous operation after the heating cycle is completed When the thermostat calls for cooling the blower operates on cooling speed When the thermostat is satisfied the blower operates on...

Page 13: ...cteristics b Adjust manifold pressure to obtain input rate 1 Remove regulator adjustment seal cap See Fig 12 2 Turn adjusting screw counterclockwise out to de crease manifold pressure or clockwise in...

Page 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Page 15: ...0 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2 3...

Page 16: ...U S A Only 575 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 600 43 2 5 43 2 6 43 2 7 43 2 7 43 2 8 9001 625 43 2 3 43 2 4 43 2 4 43 2 5 43 2 6 650 43 2 1 43 2 2 43 2 3 43 2 3 43 2 4 to 675 48 3 7 43 2 0 43 2 1...

Page 17: ...dually block off the return air after the furnace has been operating for a period of at least 5 minutes As soon as the limit has shut off the burners the return air opening should be unblocked By usin...

Page 18: ...us code 31 If hot surface igniter glows when inducer motor is disconnected shut down furnace immediately Determine reason pressure switch did not function properly and correct condition e Turn off 115...

Page 19: ...d Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate ____________ Temperature Rise A...

Page 20: ...Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog...

Reviews: