(See Fig. 10.) Select desired blower motor speed lead from
1 of the other terminals and relocate it to HEAT terminal.
See Table 9 for lead color identification. Reconnect unused
lead on SPARE terminal.

Recheck temperature rise. It must be within the air tempera-
ture rise range specified on furnace rating plate. Recom-
mended operation is at midpoint of rise or above.

3. Set thermostat heat anticipator.

The thermostat heat anticipator must be set to match the amp
draw of the electrical components in the R-W circuit. Accurate
amp draw readings can be obtained at thermostat subbase
terminals R and W. Fig. 14 illustrates an easy method of
obtaining the actual amp draw. The amp reading should be
taken after the blower motor has started. See the thermostat
manufacturer’s instructions for adjusting the heat anticipator
and for varying the heating cycle length.

NOTE:

When using an electronic thermostat, set the cycle rate for

3 cycles per hr.

CHECK SAFETY CONTROLS — The flame sensor, gas valve,
and pressure switch were all checked in the Start-up Procedures
section as part of normal operation.

1. Check primary limit control.

This control shuts off the combustion control system and
energizes the circulating-air blower motor if the furnace
overheats.

The preferred method of checking the limit control is to
gradually block off the return air after the furnace has been
operating for a period of at least 5 minutes. As soon as the
limit has shut off the burners, the return-air opening should be
unblocked. By using this method to check the limit control, it
can be established that the limit functions and operates
properly if there is a motor failure.

2. Check blocked vent safeguard switch.

The purpose of this control is to cause the safe shutdown of the
furnace during certain blocked vent conditions.

a. Disconnect power to furnace and remove vent connector

from furnace flue collar. Be sure to allow time for vent pipe
to cool down before removing.

b. Restore power to furnace and set room thermostat above

room temperature.

c. After normal start-up, allow furnace to operate for 2

minutes, then block flue collar 100 percent. Furnace should
cycle off within 2 minutes.

d. Remove blockage and reconnect vent pipe to furnace flue

collar.

Fig. 12—Redundant Automatic Gas Control

Valve

A00238

Fig. 13—Burner Flame

A89020

,

,

BURNER  FLAME

BURNER

MANIFOLD

Table 9—Speed Selector

COLOR

SPEED

FACTORY-

ATTACHED TO

Black

High

Cool

Yellow (When

present)

Medium-High

Spare

Blue

Medium-Low

Heat

Red

Low

Spare

White

Common

L2/COM

Fig. 14—Amp Draw Check With Ammeter

A96316

R

Y W G

10 TURNS

THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)

HOOK-AROUND
AMMETER

EXAMPLE:

5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS

 

=  

0.5 AMPS FOR THERMOSTAT

     ANTICIPATOR SETTING

FROM UNIT 24-V
CONTROL TERMINALS

17

Summary of Contents for WeatherMaker 8000 58YAV

Page 1: ...he unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the...

Page 2: ...ough 5 before bringing the control or yourself into contact with the furnace Put all used AND new controls into containers before touching ungrounded objects 7 An ESD service kit available from commer...

Page 3: ...changing residential construction practices We require these instructions as a minimum for a safe installation Application of this furnace should be indoors with special attention given to vent sizin...

Page 4: ...allel with or on the downstream side of the unit to avoid condensation in the heat exchangers When installed parallel with a furnace dampers or other means used to control the flow of air must prevent...

Page 5: ...ch they connect The minimum dimension of ducts must not be less than 3 in See Fig 4 AIR DUCTS Step 1 General Requirements The duct system should be designed and sized according to accepted national st...

Page 6: ...HROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Minimum of...

Page 7: ...lt should not exceed 1 1 2 in 1 Lay furnace on its back Locate and drill 5 16 in diameter hole in each bottom corner of furnace as shown in Fig 7 2 Install nut on bolt and install bolt and nut in hole...

Page 8: ...shutoff valve Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached If the furnace has been attached it is recommended tha...

Page 9: ...use ONLY a 3 amp fuse of identical size ACCESSORIES 1 Electronic Air Cleaner EAC Two quick connect terminals marked EAC 1 and EAC 2 are provided for EAC connection See Fig 10 These terminals are ener...

Page 10: ...polarity must be maintained for correct operation Thermostat wire connections at R W COM 24V and Y must be made at the 24 v terminal block on the control board The gas service pressure must not exceed...

Page 11: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOT...

Page 12: ...reverts to continuous operation after the heating cycle is completed When the thermostat calls for cooling the blower operates on cooling speed When the thermostat is satisfied the blower operates on...

Page 13: ...cteristics b Adjust manifold pressure to obtain input rate 1 Remove regulator adjustment seal cap See Fig 12 2 Turn adjusting screw counterclockwise out to de crease manifold pressure or clockwise in...

Page 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Page 15: ...0 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2 3...

Page 16: ...U S A Only 575 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 600 43 2 5 43 2 6 43 2 7 43 2 7 43 2 8 9001 625 43 2 3 43 2 4 43 2 4 43 2 5 43 2 6 650 43 2 1 43 2 2 43 2 3 43 2 3 43 2 4 to 675 48 3 7 43 2 0 43 2 1...

Page 17: ...dually block off the return air after the furnace has been operating for a period of at least 5 minutes As soon as the limit has shut off the burners the return air opening should be unblocked By usin...

Page 18: ...us code 31 If hot surface igniter glows when inducer motor is disconnected shut down furnace immediately Determine reason pressure switch did not function properly and correct condition e Turn off 115...

Page 19: ...d Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate ____________ Temperature Rise A...

Page 20: ...Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog...

Reviews: