SWEAT CONNECTION

To prevent damage to unit or service valves, observe the
following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Braze sweat connections using industry accepted methods and
materials. Do not use soft solder (materials which melt below
800°F). Consult local code requirements.

LEAK CHECKING

Leak test all joints in indoor, outdoor, and refrigerant tubing.

EVACUATE REFRIGERANT TUBING AND INDOOR COIL

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil must be evacuated to 500
microns.

IMPORTANT:

Never open system under vacuum to atmosphere

without first breaking it open with nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a minimum vacuum of 500 microns and a vacuum gage or
thermistor capable of accurately measuring this vacuum depth. The
deep vacuum method is the most positive way of assuring a system
is free of air and liquid water. (See Fig. 10.)

FINAL TUBING CHECK

IMPORTANT:

Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Step 8—Make Electrical Connections

To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

Table 2—Accessory Usage

ACCESSORY

REQUIRED FOR LONG-LINE

APPLICATIONS

*

(OVER 50 FT)

REQUIRED FOR

SEACOAST APPLICATIONS

(WITHIN 2 MILES)

Coastal Filter

No

Yes

Support Feet

No

Recommended

Puron® Balance-Port Hard Shutoff TXV

Yes†

Yes†

Puron® Liquid-Line Solenoid Valve for Heating

KHALS0401LLS

No

* For tubing line sets between 50 and 175 ft horizontal or 20 ft vertical differential refer to Application Guideline and Service Manual—Air Conditioners and Heat Pumps
Using Puron® Refrigerant. Crankcase heater and start assist are standard on two-speed units.
† Required for all applications. Factory supplied with outdoor unit.

Fig. 8—Liquid Service Valve with Sweat Adapter

Tube

A01214

SWEAT/ FLARE
ADAPTER

TEFLON
SEAL

PISTON BODY

LIQUID SERVICE VALVE

PISTON

Fig. 9—Filter Drier with Sweat Adapter Tube and

Liquid Tube

A01215

LIQUID

SERVICE

VALVE

LIQUID-LINE
FILTER-DRIER

Fig. 10—Deep Vacuum Graph

A95424

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN
SYSTEM

VACUUM TIGHT
TOO WET

TIGHT
DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

5

Summary of Contents for WeatherMaker 38YDB

Page 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Page 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Page 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Page 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Page 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Page 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Page 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Page 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Page 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Page 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Page 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Page 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Page 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Page 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Page 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Page 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Reviews: