background image

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

NOTE:

Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES

Remove access panel and control box cover to gain access to unit
wiring. Extend wires from disconnect through power wiring hole
provided and into unit control box. Size wires per NEC but not
smaller than minimum wire size shown in Product Data Digest.

The unit cabinet must have as uninterrupted or unbroken
ground to minimize personal injury if an electrical fault
should occur. The ground may consist of electrical wire or
metal conduit when installed in accordance with existing
electrical codes. Failure to follow this warning can result in an
electric shock, fire, or death.

CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for
safety. Connect power wiring to leads provided as shown in Fig.
11.

CONNECT CONTROL WIRING

Route 24v control wires through control wiring grommet and
connect to leads provided in control box. (See Fig. 12.)

Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than 100 ft from unit, as measured
along the control voltage wires, use No. 16 AWG color-coded wire
to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.

The outdoor unit requires a minimum of 27-va, 24v control power.

FINAL WIRING CHECK

IMPORTANT:

Check factory wiring and wire connections to

ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Step 9—Install Electrical Accessories

GENERAL

Refer to the individual instructions packaged with kits or acces-
sories when installing. The liquid line solenoid valve accessory is
available on these units. See Fig. 13 for wiring diagram.

Available electrical accessories include latent capacity control.

LATENT CAPACITY CONTROL (LCC)

The purpose of an LCC is to provide a dehumidification mode to
assure a 75 percent or less system sensible heat ratio. If indoor unit
installed contains an ICM blower (such as an FK4, FV4, or 40FK
fan coil or a 58UHV, 58UXV, or 58MVP gas furnace), no LCC is
required. The LCC for standard PSC blower products consists of a
standard humidistat which opens contacts on humidity rise and a
pilot duty relay with 24v coil.

NOTE:

If an LCC is desired, low-speed airflow must be main-

tained so that a minimum of 300 CFM/ton can be supplied during
high-speed LCC operation.

Step 10—Make Airflow Selections

AIRFLOW SELECTION FOR 58UHV, 58UXV FURNACES

The 58UHV, 58UXV Non-Condensing Variable-Speed Furnaces
provide high- and low-speed blower operation to match the
capacities of compressor high and low speeds. To select recom-
mended airflow, refer to the 58UHV, 58UXV Installation Instruc-
tions. These settings are made on the furnace airflow selector
board by moving the appropriate color-coded jumper wires. The
ORANGE jumper wire should be set to the HP—EFFY position
for heat pump best efficiency or HP—CMFT for heat pump
enhanced comfort. The YELLOW COOL SIZE jumper is used to
select airflow to match the needed tons of cooling. The BLUE
CFM/TON jumper wire is used to select slight adjustments to
airflow of 400, 350, or 315 CFM per ton. (See Furnace Installation
Instructions for setting required airflow.)

AIRFLOW SELECTION FOR 58MVP FURNACES

The 58MVP Condensing Variable-Speed Furnaces provide high-
and low-speed blower operation to match the capacities of com-
pressor at high and low speeds. To select recommended airflow,
refer to the 58MVP Installation Instructions. The 58MVP utilizes
a control center that allows the installing technician to select
proper airflows. For adjustments to the manual switches labeled
A/C and CF and recommended switch positions, refer to Furnace
Installation Instructions for setting required airflow. High-speed
airflow is determined by the position of the A/C switches, and
low-speed airflow is determined by the position of the CF
switches.

AIRFLOW SELECTION FOR FK4, FV4, OR 40FK FAN COILS

The FK4, FV4, and 40FK provides high- and low-speed blower
operation to match the capacities of compressor at high and low
speeds. To select recommended airflow, refer to the FK4, FV4, or
40FK Installation Instructions. The FK4, FV4, and 40FK utilizes
an EASY SELECT control board that allows the installing
technician to select proper airflows. The ORANGE SYSTEM
TYPE

JUMPER

wire

should

be

set

to

HP—EFF

or

HP—COMFORT. The BLUE AC/HP SIZE JUMPER is used to
select airflow to match the outdoor unit nominal size in tons of
cooling. The BLACK AC/HP CFM ADJUST jumper is used to
make slight adjustments to the selected airflow tonnage. (See

Fig. 11—Line Power Connections

A91306

CONTACTOR

DISCONNECT
PER N. E. C. AND/ OR
LOCAL CODES

FIELD POWER

WIRING

FIELD GROUND

WIRING

GROUND
LUG

6

Summary of Contents for WeatherMaker 38YDB

Page 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Page 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Page 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Page 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Page 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Page 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Page 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Page 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Page 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Page 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Page 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Page 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Page 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Page 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Page 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Page 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Reviews: