background image

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR)
which relieves discharge gas into compressor shell when differen-
tial between suction and discharge pressures exceeds 525 psi. The
compressor is also protected by an internal overload attached to
motor windings.

Compressor Control Contactors

Low and high capacity contactor coils are 24 volts. The electronic
control board controls the operation of the low speed (C-L) and the
high speed (C-H) contactors.

TEMPERATURE THERMISTORS

Thermistors are electronic devices which sense temperature. As
the temperature increases, the resistance decreases. Thermistors
are used to sense outdoor ambient and coil temperature. Refer to
Fig. 15 for resistance values versus temperature.

If the outdoor ambient thermistor or coil thermistor should fail, a
fault code appears at electronic control. The crankcase heater is
turned on during all off cycles.

IMPORTANT:

OUTDOOR AIR THERMISTOR PLACEMENT

Mount outdoor air thermistor underneath unit base pan lip on
control box side of unit as shown in Fig. 16. Attach to base pan
with adhesive tape. A small piece of TXV bulb insulation tape may
be used.

IMPORTANT:

If outdoor air thermistor is not properly placed

underneath base pan, unit may have nuisance thermistor out of
range faults.

Step 14—Final Checks

IMPORTANT:

Before leaving job, be sure to do the following:

1. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and
covers.

2. Tighten service valve stem caps to 1/12-turn past finger tight.

3. Leave User’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

4. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip-
ment failure, periodic maintenance must be performed on this
equipment. Frequency of maintenance may vary depending upon
geographic areas, such as coastal applications.

Table 6—Factory Defaults

FAILED COMPONENT

FUNCTION

DEFAULT

Ambient Thermistor

Defrost Initiation

Defrost is initiated based on coil

temperature and time.

One minute fan off delay in cooling

greater than or equal to 100°F

No delay function

Outdoor Coil Thermistor

Defrost Initiation and Termination

Defrost occurs at each time interval, but

terminate after 5 minutes

Table 7—Two-Speed Compressor

(Winding Resistance at 70°F ± 20°)

WINDING

024

036/037

048

060

Start (S-C)

2.280

1.850

1.459

0.740

Run (R-C)

0.770

0.745

0.552

0.356

Fig. 14—Control Board

A01192

Defrost Time
Selectors

Thermostat
Low Voltage
Connector

Reserved for
Future Use

Crankcase Heater
Connection

O.D.F. Connection

To Run
Capacitor

Thermistor
Connection

High Pressure
Switch Connector

Low Pressure
Switch Connector

Low/High Speed

Contactor

Connection

Reversing V

alve

Connection

CEBD430439-03A

SS0ID

PL1

PL2

HP/AC

C

SEV

RV

S

C

HI

LO

PL3

PL4

PL5

OCT        O

A

T       HPS          LPS

PWM2

PWM1

BRN

BLU

BLK

YEL

RED

CCH    L2   ODF            

VH             

VC

H K 3 8 E A 0 0 1

K1

CEPL130439-01

C O M M   S T A T U S

D51

D52

  A     B     C     D

0

Y2

Y1

W1

C

R

120

30

60

60

30

90

DEFROST

TIME  (MIN)

R39
R44

R42

C18

C16

R36

FORCED

DEFR

OST

1

1

1

S1

R89

R91

R87

R86

R85

J1

C31

R61

R65

R38
R33

C2

R9

1  2

Fig. 15—Resistance Values Versus Temperature

A91431

0

10

20

30

40

50

60

70

80

90

0

20

40

60

80

100

120

TEMPERATURE (DEG. F)

RESISTANCE (KOHMS)

THERMISTOR CURVE

13

Summary of Contents for WeatherMaker 38YDB

Page 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Page 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Page 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Page 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Page 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Page 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Page 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Page 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Page 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Page 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Page 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Page 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Page 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Page 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Page 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Page 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Reviews: