background image

CRANKCASE HEATER OPERATION

The two-speed control board energizes the crankcase heater during
unit’s off cycle.

OUTDOOR FAN MOTOR OPERATION

The two-speed control energizes outdoor fan any time compressor
is operating. The outdoor fan remains energized during the
1-minute compressor speed change time delay and if a pressure
switch or compressor overload should open. Outdoor fan motor
will continue to operate for one minute after the compressor shuts
off when the outdoor ambient is greater than 100°F.

After termination of a defrost cycle, the outdoor fan delays coming
on for 20 sec. This allows refrigerant system to recover outdoor
coil heat and minimize the “steam cloud” effect.

DEFROST TIME SELECTION

The defrost interval can be field selected, dependent on local or
geographical requirements. It is factory set at 90 minutes but can
be changed to either 30, 60, or 120 minutes. To select defrost time,
set dip switches located on the left side of the unit board (See Fig.
14). See Table 5 for Defrost Dip Switch Settings.

DEFROST

The dual capacity control logic for defrost function is time and
temperature initiated, time or temperature terminated.

Defrost only occurs at outdoor temperatures less than 50°F. The
control initiates defrost when outdoor coil thermistor is 30°F (±2°)
or less, and selected defrost time (interval) has been accumulated

WIRING DIAGRAM NOTES:

1. Wiring must conform to NEC or local codes.

2. Underlined letter on thermostat terminal indicates its usage. For example: O/W2 means O is energized in cooling mode.

3. Refer to indoor unit Installation Instructions for any additional features and wiring information.

4. Non-Programmable Model 2S01–B, when used in heat pump installations (jumper R19 NOT cut), uses O/W2 to control reversing valve.

5. Furnace must control its own second-stage operation via furnace control algorithms. Refer to furnace Installation Instructions for proper

setup.

6. To activate dehumidify function on FK4, FV4, or 40FK, remove J1 jumper at fan coil control board.

7. Heat pump MUST have a high-pressure switch for dual fuel applications.

8. Outdoor air temperature sensor must be attached in all dual fuel applications.

9. Thermidistat Dip Switch No. 1 should be set in ON position for heat pump installations.

10. Thermidistat Dip Switch No. 2 should be set in the ON position for dual capacity compressor operation.

11. Thermidistat Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.

12. To activate dehumidify feature on current style 58UHV, 58UXV variable-speed 80-percent noncondensing furnaces, disconnect green

(dehum) wire from G on furnace control board and connect to dehumidify terminal DHUM on Thermidistat.

13. Dual Fuel Dip Switch–D (no. 4) must be set in the ON position for dual capacity compressor operation.

14. The DE jumper located next to the DHUM terminal must be removed to enable the DEHUM input.

A01222

LEGEND

24 VOLT FACTORY WIRING

24 VOLT FIELD WIRING

FIELD SPLICE CONNECTION

RELAY SPDT, PILOT DUTY
24-V COIL (HN61KK324)
OR EQUIVALENT

HUMIDISTAT, OPENS ON
HUMIDITY RISE (HL38MG026)

AIRFLOW SELECTOR

R1

H

AFS

Fig. 13—Typical Solenoid Valve Wiring

A01191

40FK

FK4/FV4

FAN COIL

TWO-SPEED

HEAT PUMP

24 VAC HOT

24 VAC COM

FAN

COOL/HEAT
STAGE 2

HEAT STAGE 3

RVS COOLING

N/A

OUTDOOR
SENSOR

CONNECTION

COOL/HEAT
STAGE 1

J2 JUMPER

J1 JUMPER

R

C

G

Y/Y2

W/W2

O/W2

Y1

B

S1

S2

DH

R

G

C

Y/Y2

W1

W2

O

Y1

R

C

Y2

W1

O

Y1

Y1

Y2

Y2

Y1

LLS

11

Summary of Contents for WeatherMaker 38YDB

Page 1: ...ing label Electrical shock can cause personal injury or death Puron R 410A systems operate at higher pressures than standard R 22 systems Be certain that service equipment is rated for R 410A Some R 2...

Page 2: ...e of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit On rooftop applic...

Page 3: ...lizer tube 9 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter 10 Attach TXV bulb to horizontal section of suction line using bulb strap provided See Fig 6C Insulate bulb...

Page 4: ...o indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition Tubing diameters listed in Table 1 are adequate for equivalent lengths up to 50...

Page 5: ...d tight Step 8 Make Electrical Connections To avoid personal injury or death do not supply power to unit with compressor terminal box cover removed Be sure field wiring complies with local and nationa...

Page 6: ...HV 58UXV or 58MVP gas furnace no LCC is required The LCC for standard PSC blower products consists of a standard humidistat which opens contacts on humidity rise and a pilot duty relay with 24v coil N...

Page 7: ...are not equipped with Schrader valves To prevent personal injury make sure gage manifold is connected to the valve gage ports before moving valves off fully back seated position Wear safety glasses an...

Page 8: ...ions See Table 4 for codes and definitions Table 4 also provides the order of signal importance NOTE Only one code will be displayed on the outdoor unit control board the most recent with the highest...

Page 9: ...TROL MODEL RH See notes 1 2 3 6 9 and 10 A01421 O W2 W W1 Y1 W2 G R THERMIDISTAT CONTROL MODEL RH SINGLE STAGE FURNACE TWO SPEED HEAT PUMP W G Y C Y2 W1 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL...

Page 10: ...B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 FURNACE COOL HEAT STAGE 1 COMPRESSOR LO COOL HEAT STAGE 2 COMPRESSOR HI RVS COOLING FAN 24 VAC HOT 24 VAC COMM RVS SENSING N A OUTDOOR SENSOR CON...

Page 11: ...and wiring information 4 Non Programmable Model 2S01 B when used in heat pump installations jumper R19 NOT cut uses O W2 to control reversing valve 5 Furnace must control its own second stage operatio...

Page 12: ...oses anytime after the 15 minute delay then resume operation on call for Y1 and or Y2 HEATING VAPOR PRESSURE SWITCH PressureGuard This outdoor unit is equipped with a heating vapor pressure limiting d...

Page 13: ...ve User s Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE F...

Page 14: ...PNK YEL PNK YEL PNK BRN BRN BLK BLK BLK ORN RVS ORN RED BLU CH 11 21 23 23 YEL BLK BLK BLK CL 11 21 H C START COMP RELAY BRN CAP L2 L1 EQUIPGND DUALCAPACITY A B C D BLU BRN BRN BLK YEL BRN VPS BLK C O...

Page 15: ...RSUPPLY TIME MIN DEFROST VH L 2 ODF CCH VC RED YEL BLK BLU BRN PL5 PL4 PL3 YEL BLU BRN YEL OCT OAT LPS HPS Fig 19 Wiring Diagram 060 A01420 CONNECTION DIAGRAM OCT t LPS HPS OAT t LO HI TO INDOOR UNIT...

Page 16: ...1 38ydb3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 533 8004...

Reviews: