Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
70
NOTE
Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
Status
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Status
Point Name/Description
Range
Terminal Mode
– The controller's current operating status.
R: Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
Term Type
– The type of zone terminal that the controller is installed on.
R: Single Duct
Parallel Fan
Series Fan
Space Temperature
- Prime Variable
– The space temperature value currently used for
control.
R: -56 to 245°F
(-48.9 to 118.3°C)
Primary Airflow
– The current airflow measured through the primary air damper.
R: 0 to 99999 cfm
(liters/second)
Damper Position
– The current damper position.
R: 0 to 100%
Supply Air Temperature
– Displays the current supply air temperature.
R: -56 to 245°F
(-48.9 to 118.3°C)
Heating Capacity
– The current reheat capacity when the zone is configured for reheat.
R: 0 to 100%
Baseboard Heating Capacity
– The current baseboard heat capacity when the zone is
configured for Combination Baseboard or Non-ducted Heat.
R: 0 to 100%
Outdoor Air Temperature
– The current outdoor air temperature from a linked air
source, if available, or from another network source.
R: -56 to 245°F
(-48.9 to 118.3°C)
Fan
– The status of the terminal fan if
Term Type
is
Parallel Fan
or
Series Fan
.
R: On/Off
Space Relative Humidity
– The current space relative humidity if
Service Configuration
>
Hardwired Sensor
is set to
RH Sensor
or, you have a valid ZS RH sensor.
R: 0 to 100%rh
Indoor Air Quality CO2 (ppm)
– The current IAQ value if
Service Configuration
>
Hardwired Sensor
is set to
CO2 Sensor
or, you have a valid ZS CO
2
sensor.
R: 0 to 5000ppm
Appendix A: VAV Zone II Points/Properties