Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
87
Zone Temp
- Configure additional ZS or wireless temperature sensors used on the VAV
Zone II.
Use
- Check to include ZS or wireless sensors' value in the
Combined Algorithm
(
Average
is the default).
Raw Value
- Displays sensed temperature for each ZS or wireless temperature
sensor's address
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS or wireless sensor's sensed value.
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
zone temperature to
calculate the
Corrected Value
for temperature control.
D:
(Index) Area
- (1) Main
Sensor
Use -
checked
Calibration
- 0
Combination Algorithm
-
Average
Input Smoothing
- None
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- .1
Zone Humidity
- Configure additional ZS or wireless humidity sensors used on the VAV
Zone II.
Use
- Check to include ZS or wireless sensors' value in the
Combined Algorithm
(
Maximum
is the default).
Raw Value
- Displays sensed humidity for each ZS or wireless humidity sensor's
address
Calibration
- If needed, enter value to adjust the
Corrected Value
from the
Raw
Value
, in order to calibrate an individual ZS or wireless sensor's sensed value.
Combination Algorithm
- Use
Average
,
Maximum
, or
Minimum
ZS or wireless
humidity to calculate the
Corrected Value
for humidity control.
D:
(Index) Area
- (1) Main
Sensor
Use -
unchecked
Calibration
- 0
Combination Algorithm
-
Maximum
Input Smoothing
- None
Show on Sensors
-
Calculated Value
Display Resolution
- 1
COV Increment
- 1