Appendix D: BACnet points list for the VAV Zone II Fan Terminal
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
102
BACnet
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Occupied Cooling Setpoint
R/W
°F
75
occ_cl_stpt
AV:3001
Reset Filter Alarm
R/W
0=Off
1=On
Inactive (0) filter_rntm_clr
BV:7517
Setpoint Adjustment
R/W
0=Disable
1=Enable
Active (1)
stpt_adj_enable
BV:1013
Shutdown
R/W
0=Inactive
1=Active
Active (1)
shutdown
BV:9001
VAV Reheat
R/W
0=Disable
1=Enable
Active (1)
vav_reheat
BV:1029
Air Source Mode
R
1=OFF
2=WARM-UP
3=HEAT
4=COOL
5=FREECOOL
6=PRESSURIZE
7=EVACUATE
8=VENT
link_ahu_mode
MSV:2005
BAS On / Off
R/W
1=Inactive
2=Occupied
3=Unoccupied
1
keypad_ovrde
MSV:1001
Optimal Start Type
R/W
1=None
2=Temp Compensated
3=Learning Adaptive
2
start_type
MSV:2009
Space Temp Source
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
spt_status
MSV:2003
Terminal Mode
R
1=Off
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
7=Dehumidify
8=Reheat
9=Pressurize
10=Evacuate
11=Shutdown
12=IAQ Override
13=Air Balancing
terminal_status
MSV:2006
Terminal Type
R
1=Single Duct
2=Parallel Fan
3=Series Fan
terminal_type
MSV:2007
Zone Type
R
1=Slave
2=VVT Master
3=VAV Master
zone_type
MSV:2008
Airside Linkage Status
R
0=Normal
1=Alarm
air_linkage_fail
BV:7030
Filter
R
0=Clean
1=Dirty
filter_alarm
BV:7017
High SPT
R
0=Normal
1=Alarm
spt_hi_alarm
BV:7011
Indoor Air Quality
R
0=Normal
1=Alarm
iaq_alarm
BV:7005
Low SPT
R
0=Normal
spt_lo_alarm
BV:7012