Start-up
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
46
Damper Command
Action
Cool Max
Forces the damper to its maximum cooling position. Calibration fields apply only if the
primary use of this damper is cooling.
Occupied Min
Forces the damper to its minimum occupied position and enables the
Occupied Min
Flow
calibration fields.
Damper Close
Forces the damper to its full closed position.
Heat Max
Forces the damper to its maximum heating position. Calibration fields apply only if
the primary use of the damper is heating.
Automatic
Returns control of the damper to the control program.
You must perform this step
when you finish test and balance.
Upload calibration values to the i-Vu® application
CAUTION
If your system has an i-Vu® user interface, you
must
run the Test and Balance report in the i-Vu®
application after using VAV Zone II. Running the report uploads the values from the controller to the i-Vu®
application. You will lose all your calibrations if you download to the controller in the i-Vu® interface before
running this report.
1
In the i-Vu® interface, select the top level in the navigation tree.
2
Click
Reports
>
Commissioning
>
Test and Balance
.
3
On the
View
tab, click
Run
.
Go to Step 4: Run a report (Optional).
Run a report in VAV Zone II (Optional)
After balancing, you can run a report (.htm file) in Test & Balance that shows each controller's calibrated values
and design values. You can view or edit the file in Microsoft Excel, Microsoft Word, or any web browser.
1
Select
Session
>
Report
.
2
Select an existing report or type a name in the
File Name
field.
3
Click
Save
.
4
If you chose an existing report in step 2, select
Append
to add to the report or
Overwrite
to replace the report.