Appendix D: BACnet points list for the VAV Zone II Fan Terminal
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
103
BACnet
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Occupied Cooling Setpoint
R/W
°F
75
occ_cl_stpt
AV:3001
1=Alarm
Network OAT
R
0=Normal
1=Alarm
oat_fail
BV:7029
Space Relative Humidity
R
0=Normal
1=Alarm
sprh_hi_alarm
BV:7018
Space Temp Sensor
R
0=Normal
1=Alarm
spt_fail
BV:7001
Supply Air Temperature
R
0=Normal
1=Alarm
sat_alarm
BV:7004
Wireless Battery Strength Alarm
R
0=Normal
1=Alarm
ws_batt_alarm
BV:7064
Wireless Signal Strength Alarm
R
0=Normal
1=Alarm
ws_sig_alarm
BV:7065
ZS/WS Sensor Configuration
R
0=Normal
1=Alarm
zs_config_fail
BV:7055