Wiring field-supplied actuators to the analog output
TruVu™ VVTBP
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
33
You can wire a high-torque actuator or parallel actuators to the controller's 0
–
10 Vdc analog output.
NOTE
You cannot use the TV-VVTBP-E2's actuator if wiring external actuator(s) to the analog output.
High-torque actuators
You can wire one of the following Belimo actuators to the TV-VVTBP-E2's analog output instead of using the
controller's 45 in.-lb (5 Nm) actuator.
NMX24-MFT P-10028
90 in.-lb (10 Nm) actuator with 0
–
10 Vdc control and 0
–
10 Vdc
feedback
AMX24-MFT P-10028
180 in.-lb (20 Nm) actuator with 0
–
10 Vdc control and 0
–
10 Vdc
feedback
1
Install the actuator according to the manufacturer's instructions.
2
Wire the actuator to the controller using the diagram below.
NOTE
For proper operation and to prevent damage to the devices, use the same polarity for the actuator's power
and the TV-VVTBP-E2's power.
Wiring field-supplied actuators to the analog output