To adjust input and output properties
TruVu™ VVTBP
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
29
Input values
Input
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAI)
0-5 Vdc
0
–
5 Volt
Linear Full Range
Engineering values associated
with 0 Vdc (Min) and 5 Vdc (Max)
1
No Translation
N/A. The input microblock's
value will be the raw voltage of
the input.
0-10 Vdc
0
–
10 Volt
Linear Full Range
Engineering values associated
with 0 Vdc (Min) and 10 Vdc
(Max)
No Translation
N/A. The input microblock's
value will be the raw voltage of
the input.
2-10 Vdc
0
–
10 Volt
Linear w/Offset,
2
–
10 Volts
Engineering values associated
with 2 Vdc (Min) and 10 Vdc
(Max)
Thermistor
Thermistor
Select your Thermistor type or
set up and select a
Non-Linear,
Custom Table
2
N/A
Pulse to Analog (BPTA)
3
Pulse Counter
Dry Contact or Binary
Input
N/A
N/A
Binary (BBI)
Dry Contact
Dry Contact
N/A
N/A
Binary Contact
Binary Contact
N/A
N/A
Special (BI)
4
Binary
Special
Online flow sensor status
N/A
1
The sensor reads a value and sends a corresponding signal (Volts) to the TV-VVTBP-E2's physical input. The
Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value
used in subsequent control logic.
2
You can set up a
custom translation table
(page 49) on the driver's
Custom Translation Tables pages in the i-
Vu® interface.
3
The control program must have one Pulse to Analog Input microblock for each pulse counting input.
4
The special binary input indicates a communication loss to the airflow sensor. You can use this in your control
program to select the actuator movement in the case of flow sensor fault. Sensor reconnection is detected
automatically and a power cycle is not required. In the microblock popup, under
Hardware Configuration
, set
Expander
to
0
,
Input Number
to
110
, and
I/O Type
to
Special
. To detect a flow sensor fault on the ZASF-A, use
Input Number 111
.