Mounting the TV-VVTBP-E2
TruVu™ VVTBP
-E2
©2022 Carrier.
Installation and Start-up Guide
All rights reserved.
12
9
Hold down the actuator release button, rotate the damper to verify that it opens and closes, then release the
button.
10
Connect the tube provided to either one of the controller's airflow ports. Using 1/4" poly tubing, connect the
other end to a duct static pressure probe (for example, Dwyer Instruments part #A-491, or the equivalent, for
a 6” length probe) located in the supply air duct downstream of the
bypass damper, but before the first
branching of ductwork.
11
Leave the remaining airflow port open if using a ducted return, or connect it to room space if using plenum
return.