Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
122
Point Name/Description
Default/Range
Hardwired Sensor
–
The type of sensor used on the controller's IN-01 hardwire input.
This setting determines the control channel input function.
Options:
RH Sensor
–
Relative humidity for zone dehumidification
IAQ Sensor
–
Indoor air quality for DCV control
NOTE
RH and IAQ are also available with communicating ZS RH and CO
2
sensors.
D:
R:
None
None
RH Sensor
IAQ Sensor
RH Control
–
Enables or disables zone dehumidification control if valid RH sensor
values are available.
D:
R:
Disable
Disable/Enable
DCV Control
–
Enables or disables demand control ventilation control.
D:
R:
Disable
Disable/Enable
Min Setpoint Separation
–
Minimum separation that must be maintained between the
heating and cooling setpoints.
D:
R:
4 °F (2.2 °C)
2 to 10 °F
(1.1 to 5.5 °C)
Occ Override Normal Logic State
–
The normal state of the controller's IN-04 input. If
the input's contact is the same state as the configured state, the controller follows its
controlling schedule. If the contact is in the opposite state of the configured state, the
controller is forced into the unoccupied mode.
D:
R:
Open
Open/Closed
RH Sensor Min Input Volts
–
The lowest voltage that should be read from the hardwired
relative humidity (RH) sensor.
D:
R:
0.00 V
0 to 5.00 V
RH Sensor Max Input Volts
–
The highest voltage that should be read from the
hardwired RH sensor.
D:
R:
5.00 V
0 to 5.00 V
RH Sensor Value @ Min Volts
–
The % relative humidity that correlates to the hardwired
RH sensor's low voltage reading.
D:
R:
0%
0 to 99%
RH Sensor Value @ Max Volts
–
The % relative humidity that correlates to the hardwired
RH sensor's high voltage reading.
D:
R:
100%
0 to 100%
CO2 Sensor Min Input Volts
–
The lowest voltage that should be read from the
hardwired CO
2
sensor.
D:
R:
1.00 V
0 to 5.00 V
CO2 Sensor Max Input Volts
–
The highest voltage that should be read from the
hardwired CO
2
sensor.
D:
R:
5.00 V
0 to 5.00 V
CO2 Sensor Value @ Min Volts
–
The ppm value that correlates to the hardwired CO
2
sensor's low voltage reading.
D:
R:
0 ppm
0 to 9999 ppm
CO2 Sensor Value @ Max Volts
–
The ppm value that correlates to the hardwired CO
2
sensor's high voltage reading.
D:
R:
2000 ppm
0 to 9999 ppm