Adjusting the TV-VAVB3-E2 driver properties
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
80
Custom Translation Tables
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to provide on the output wire of the Analog Input microblock. In the navigation
tree, select
Custom Translation Table #1
,
#2
, or
#3
. The
Properties
page has instructions.
For the input to use the translation table, go to the control program's
Properties
page >
I/O Points
tab. Click the
analog input in the
Name
column. On the
Details
tab, set
Sensor Type (Scaling Method)
to
Non-Linear, Custom
Table #__
.
BACnet Controller Properties
The
BACnet Controller Properties
page provides the following information plus the items described in the table
below:
•
The TV-VAVB3-E2's Ethernet MAC address
•
Whether
Port S1
is being used for MS/TP and is disabled
NOTE
The options shown on the page change according to your controller's settings.
MS/TP Configuration on Port S1
Address
For Port S1
—
A unique address on the MS/TP network.
MS/TP Autobaud
To enable autobaud, select
Yes
. This device will receive its baud rate from the
master device.
MS/TP Baud Rate
Set this to a baud rate that all other devices on the MS/TP network are set to.
Max Masters
To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
Max Info Frames
This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP
Set
Max Info Frames
to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
End of Network Switch
Status
Port S1 End of Network
This displays the state of the
End of Net?
termination switch for Port S1.
IP Configuration
Allow setup of IP addressing
through an external tool
When this field is enabled, you can set up IP addressing through a tool. IP
addressing is typically set up through the Service Port.