Appendix D: BACnet points list
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
143
BACnet
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Standby Offset
R/W
°F
0
stdby_offset
AV:1017
Supply Air Temperature
R
°F
sa_temp
AV:1008
System Outdoor Air Temperature
R/W
°F
-999
system_oat
AV:1901
System Setpoint Adjustment
R/W
°F
-999
system_stpt_adj
AV:1913
System Space AQ
R/W
ppm
-999
system_iaq
AV:1903
System Space RH
R/W
%
-999
system_rh
AV:1904
System Space Temperature
R/W
°F
-999
system_spt
AV:1902
Airside Linkage Status
R
0=Not Active
1=Active
a_link_status
BV:2601
Fan
R
0=Off
1=On
sfan_status
BV:1003
Heat Enable
R/W
0=Disable
1=Enable
Active (1)
ht_enable
BV:1012
Occupancy Status
R
0=Unoccupied
1=Occupied
occ_status
BV:2008
Reset Filter Alarm
R/W
0=Off
1=On
Inactive (0) filter_rntm_clr
BV:7517
Setpoint Adjustment
R/W
0=Disable
1=Enable
Active (1)
stpt_adj_enable
BV:1013
Shutdown
R/W
0=Inactive
1=Active
Active (1)
shutdown
BV:9001
VAV Reheat
R/W
0=Disable
1=Enable
Active (1)
vav_reheat
BV:1029
Air Source Mode
R
1=OFF
2=WARM-UP
3=HEAT
4=COOL
5=FREECOOL
6=PRESSURIZE
7=EVACUATE
8=VENT
link_ahu_mode
MSV:2005
BAS On / Off
R/W
1=Inactive
2=Occupied
3=Unoccupied
1
keypad_ovrde
MSV:1001
Optimal Start Type
R/W
1=None
2=Temp Compensated
3=Learning Adaptive
2
start_type
MSV:2009
Space Temp Source
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
spt_status
MSV:2003
Terminal Mode
R
1=Off
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
terminal_status
MSV:2006