Appendix D: BACnet points list
TruVu™ VAVB3
-E2
CARRIER CORPORATION ©2022
Installation and Start-up Guide
All rights reserved
144
BACnet
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
7=Dehumidify
8=Reheat
9=Pressurize
10=Evacuate
11=Shutdown
12=IAQ Override
13=Air Balancing
Terminal Type
R
1=Single Duct
2=Parallel Fan
3=Series Fan
terminal_type
MSV:2007
Zone Type
R
1=Slave
2=VVT Master
3=VAV Master
zone_type
MSV:2008
Airside Linkage Status
R
0=Normal
1=Alarm
air_linkage_fail
BV:7030
Filter
R
0=Clean
1=Dirty
filter_alarm
BV:7017
High SPT
R
0=Normal
1=Alarm
spt_hi_alarm
BV:7011
Indoor Air Quality
R
0=Normal
1=Alarm
iaq_alarm
BV:7005
Low SPT
R
0=Normal
1=Alarm
spt_lo_alarm
BV:7012
Network OAT
R
0=Normal
1=Alarm
oat_fail
BV:7029
Space Relative Humidity
R
0=Normal
1=Alarm
sprh_hi_alarm
BV:7018
Space Temp Sensor
R
0=Normal
1=Alarm
spt_fail
BV:7001
Supply Air Temperature
R
0=Normal
1=Alarm
sat_alarm
BV:7004
Wireless Battery Strength Alarm
R
0=Normal
1=Alarm
ws_batt_alarm
BV:7064
Wireless Signal Strength Alarm
R
0=Normal
1=Alarm
ws_sig_alarm
BV:7065
ZS/WS Sensor Configuration
R
0=Normal
1=Alarm
zs_config_fail
BV:7055