Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
75
Optimal Start Type
– The method used to change from unoccupied to occupied setpoint.
Options:
None
– Unit will not change to occupied setpoint until the scheduled time or the unit goes into an
occupied mode. Setpoints do not ramp, but change immediately from unoccupied to occupied
values.
Temp Compensated
– Unit changes to occupied setpoints at a variable time prior to the occupied
time, which is calculated by the current difference between space temperature and the
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change
immediately from unoccupied to occupied values.
Learning Adaptive Start
– Unit gradually changes to occupied setpoints by adjusting the
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the time
scheduled occupancy
begins.
D:
R:
Temperature
Compensated
None
Temperature
Compensated
Learning
Adaptive
Heat Start K factor (min/deg)
– If
Optimal Start Type
is
Temp Compensated
, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is below the occupied heating setpoint (including any setpoint offset).
D:
R:
15.00
0 to 99
Cool Start K factor (min/deg)
– If
Optimal Start Type
is
Temp Compensated
, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is above the occupied cooling setpoint (including any setpoint offset).
D:
R:
15.00
0 to 99
Occ Relative Humidity Setpoint
– The percentage of relative humidity in the space during
occupancy that will energize BO - 6 (Humidi-MiZer™).
D:
R:
60%rh
0 to Unoccupied
RH Control
Setpoint
Unocc Relative Humidity Setpoint
– The percentage of relative humidity in the space during the
unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).
D:
R:
95%
30 to 100%
DCV Max Ctrl Setpoint
– The design difference between indoor and outdoor CO2 levels.
D:
R:
650ppm
0 to 9999 ppm
Power Exhaust Setpoint
- The outside air damper position at which the controller energizes the
Power Exhaust relay.
Configuration
>
Service Configuration
>
Economizer Exists
must be set to
Yes
, and
Configuration
>
Service Configuration
>
Continuous Occupied Exhaust
must be set to
No
.
D:
R:
50% Open
20 to 90% Open