Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
82
Maintenance
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Maintenance
Point Name/Description
Default/Range
Unit
Occupancy Status
– The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
R: Unoccupied/Occupied
Indicates the current status of the system:
Temp Compensated Start
Learning Adaptive Start
R: Inactive/Active
Pre-Occ Purge
– Indicates if the pre-occupancy purge cycle is active.
R: Inactive/Active
Space Temp Source –
The source of the controlling space temperature value.
Options:
Sensor Failure
– No valid space temperature or sensor status = failed.
SPT Sensor
– An SPT sensor is connected to the controller's Rnet port.
T55/56
– A T55, T56, or T59 sensor is connected to the controller's I/O terminals.
Network
– A network temperature sensor is bound to the controller's space
temperature AV.
Airside Linkage
– The space temperature from a linked terminal.
Locked Value
–The controller's space temperature input has been manually locked at a
value.
ZS Sensor
– A ZS sensor is connected to the controller's Rnet port.
R: Sensor Failure
SPT Sensor
T55/T56
Network
Airside Linkage
Locked Value
ZS Sensor
Setpoint Adjustment
– Indicates the amount of offset applied if you configured the
space sensor as a type of T56. Set the display value range in
Setpoint Adjustment
Range
.
R: _°F/C
Effective Heat Setpoint
– The current heating setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Effective Cool Setpoint
– The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Relative Humidity Source –
The source of the relative humidity value.
R: N/A
Local
Network
Linkage
Locked Value
Linkage & Local
ZS Sensor
Linkage & ZS Sensor
Summary of Contents for RTU Open v3