INFORMATION MENU (3)

ITEM

FORMAT

UNITS

0

±

nn.n

°

C

LOFF

-

L-On

-

L-Sc

-

CCn

-

rEM

-

tStA

-

OFF

-

rEADY

-

dELAY

-

StOPPing

-

running

-

triPout

-

OvErridE

-

dEFrOSt

-

OCCUPIEd

-

UNOCCUPIEd -

COOL

-

HEAT

-

StAndbY

-

ALArM

-

ALErt

-

MAStEr

-

SLAvE

-

1 [1]

nn
-

2 [2]

-

occu
unoc
Forc

3

nn.n

minutes

4 [2]

HEAt

-

COOL

-

StbY

-

FrSt

-

5

nnn

%

6 [2]

nnn

%

7

YES

-

nnn

-

Forc

-

8

-

SP-1
SP-2
SP-3
AUtO

9

±

nn.n

°

C

10

±

nn.n

°

C

 Forc

11

nn.n

°

C

12

nn.n

°

C

13 [2]

0-6

-

4.3.5 - Description of the Information menu

DESCRIPTION

Automatic display  mode

. It cycles through the following displays:

1:

Controlled space temperature:

 temperature of the water that the unit tries to maintain at the control point.

2:

Unit operating type

Local Off
Local On
Local On - based on unit clock.
CCN Control.
Remote Control
Thermostat control

3:

Unit status

Off: Unit is stopped and not authorised to start.
Ready: Unit is authorised to start
Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can be
configured in the User Configuration menu.
Stopping: Unit is currently stopping.
On: Unit is running or authorised to start.
Fault shutdown.
Limit: The operating conditions do not allow total unit operation.
Defrost: One circuit is in defrost mode.

4:

Unit occupied/unoccupied status

Occupied: Unit in occupied mode
Unoccupied: Unit in unoccupied mode

5:

Heating/cooling operating mode

Cooling: Unit operates in cooling mode
Heating: Unit operates in heating mode
Standby: Unit is in auto cooling/heating changeover mode, and is in standby

6:

Alarm mode

Alarm: Unit is totally stopped because of failure.
Alert: Unit is in failure but not completely stopped.

7:

Master/Slave status

Master: The master/slave control is active and the unit is the master
Slave: The master/slave control is active and the unit is the slave

Active mode codes.

 Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode code

is displayed causes a character text expansion to be scrolled across the four-digit  display. See the description in the following table

This item indicates the current 

unit occupied/unoccupied

 mode.

Occupied
Unoccupied
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable is forced through CCN.

Start-up delay.

 This item indicates the minutes left before the unit can be started. This delay at start-up is always active after the unit

has been switched on. The delay can be configured in the User Configuration 1 menu.

Heating/cooling mode.

 This item indicates whether the unit is in cooling or heating. Displayed if the unit controls a boiler.

Heating
Cooling
Standby: Unit is in auto cooling/heating changeover mode, and is in standby.
Frost protection mode active.

Total active capacity of compressors

.

Active additional heating stages.

Unit demand limit based on the configuration. See section 4.3.11.3.

Yes - demand limit active
No - demand limit inactive
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable is forced through CCN.

Setpoint select in local mode.

 This point is read/write accessible. Displayed only when the unit is LOFF or L-On operating type.

SP-1 = occupied setpoint
SP-2 = unoccupied setpoint
SP-3 = frost protection setpoint
AUtO = active setpoint depends on schedule 2 (setpoint selection schedule). See section 5.5.1 & 4.3.11.6.

Active room temperature setpoint.

Active temperature control point.

 This is the setpoint used by the controller to adjust the room temperature.

Control point = active se offset. See section 5.5.
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable is forced through CCN.

Room dead band active in 

°

C

This is the dead band used by the control to regulate the room temperature. See section 5.5.1. The control uses two dead bands for the
room temperature control: one is in the occupied period, the other in the unoccupied period. These two values can be configured by the
user in the Setpoint Menu.

Room temperature in 

°

C

This is the room temperature calculated following actions taken by the room sensors. If the unit only has one room sensor, it is the
value read by that sensor. If the unit has several optional temperature sensors, it depends on the configuration (see section 4.3.11.3).
It can be the middle, minimum or maximum value read by the sensors.

Economiser status

This item indicates the economiser status. See section 5.16 for the economiser control description.
0 = Initial value
1 = Eco function is off
2 = CCN forced change in Economiser position
3 = Purge mode active
4 = Economiser set to minimum position
5 = Not used
6 = Enthalpy is high; Economiser set to minimum position

1

This item is masked when nil.

2

This item is displayed in certain unit configurations only.

Summary of Contents for PRO-DIALOG PLUS 50AZ

Page 1: ...1 50AZ UZ PRO DIALOG Control for rooftop units 50 Hz Installation operationandmaintenanceinstructions...

Page 2: ...thermostat control 23 5 2 Start stop control 24 5 3 Indoor fan on off control 24 5 4 Calculating the room temperature 25 5 5 Room temperature control point 25 5 6 Heating cooling mode 25 5 7 Anti fre...

Page 3: ...G Plus is a system for controlling rooftop air conditioners of the following types Single and dual circuit Air conditioners and reversible heat pumps PRO DIALOG Plus maintains room temperature at the...

Page 4: ...erating properly The red LED flashing for a 2 second period on the NRCP BASE board indicates correct operation A different rate indicates a board or a software failure On dual circuit units or units e...

Page 5: ...tact 1 start stop Contact 2 demand limit selection Contact 3 setpoint selection 1 Contact 4 setpoint selection 2 Connection to CCN Connector channel J3 CH24 J3 CH24 J4 CH8 J4 CH9 J4 CH10 J4 CH11a J12...

Page 6: ...a c 48 V d c max 20 V a c or V d c 3 A max 80 mA min external power supply Connector 4 pin WAGO 734 168 pitch 3 5 One per board needed 24 V a c 20 mA Connector 8 pin Wago 734 168 pitch 3 5 One per boa...

Page 7: ...fied INPUTS menu Displays the status of the unit digital and analogue inputs OUTPUTS TESTS menu Displays the status of the unit outputs and enables them to be tested CONFIGURATIONS menu Displays the u...

Page 8: ...art Stop button OPERATINGTYPES 4 DIGIT DISPLAY DESCRIPTION LOFF Local Off The unit is halted in local mode L On Local On The unit is in local control mode and is authorised to start L Sc Local On time...

Page 9: ...button again to validate the change or to access the sub menu The LED for the menu to which the item belongs as well as the two digit display then stop flashing indicating that modification mode no lo...

Page 10: ...r 2 SCHEDULE 1 SCHEduLE 1 HOLIDAYS HoLidAy HOUR DATE dAtE BROADCAST brodCASt SERVICE 1 SErviCE 1 SERVICE 2 SErviCE 2 SERVICE 3 SErviCE 3 HOLIDAYS 3 HoLidAy 3 HOLIDAYS 4 HoLidAy 4 HOLIDAYS 5 HoLidAy 5...

Page 11: ...nt room humidity unoccu pied mode Dead band room humidity unoccu pied mode Purge minimum outside temp Purge maximum outside temp Purge duration Setpoint air quality INPUTS Indoor fan status Filter add...

Page 12: ...tes left before the unit can be started This delay at start up is always active after the unit has been switched on The delay can be configured in the User Configuration 1 menu Heating cooling mode Th...

Page 13: ...ed period that has to last two hours and the outside temperature is inside the limits defined by the user Setpoint Menu the economiser is kept fully open for a configurable duration Setpoint Menu see...

Page 14: ...de outside temperature for zero offset 6 1 nnn C 4 4 60 Cooling mode outside temperature for maximum offset 7 1 n C 0 16 7 Cooling mode maximum offset value 8 1 n 10 80 Humidity setpoint occupied mode...

Page 15: ...o the compressor is switched on for 10 seconds only It is then not possible to restart the compressor for a further 30 seconds When the test is completed the following is displayed Fail displayed if t...

Page 16: ...own LOFF To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key longer than 2 seconds to activate the modification mode The password is automatically r...

Page 17: ...rotection mode selection in unoccupied mode Room temperature calculation type selection Indoor fan operation type selection Purge function selection Occupied period extension selection Smart Start fac...

Page 18: ...lection in cooling mode This is the number of compressor stages authorised for operation when the demand limit contact is closed See sections 3 5 and 5 9 9 1 0 1 2 3 4 5 5 Demand limit selection in he...

Page 19: ...FORMAT COMMENTS 0 dAtE MEnu When selected this item authorises return to the previous menu 1 n1 n2 n3 n4 Current time setting 00 00 to 23 59 n1 n2 hours 00 to 23 The first time the Enter button is co...

Page 20: ...cters in the 4 digit display flash so that hours can be adjusted n3 n4 minutes 00 to 59 Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjust...

Page 21: ...he start of daylight 1 to 1440 minutes saving time 9 nn Daylight saving stop month In this mode you enter the month in which the broadcaster will adjust its time for the end of 1 to 12 daylight saving...

Page 22: ...M100 nnn nnn nnn nnn UNITS hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 minutes minute...

Page 23: ...stage is started Single circuit reversible unit Contact G open the internal fan is stopped and the econo miser is closed Contact G closed the internal fan is activated and the economiser is opened to...

Page 24: ...marises the unit control type and stop or go status with regard to the following parameters Operating type this is selected using the start stop button on the front of the user interface Remote start...

Page 25: ...the beginning of the occupied period The control calculates an antici pated start up value in minutes based on a user configurable factor anticipated start up factor expessed in minutes degrees that m...

Page 26: ...ach compressor value weighted by the operating time This means the compressor with the least number of start ups is always the first to start up and the first to shut down 5 12 Head pressure control C...

Page 27: ...n it enables the position of the economiser to be continually adjusted in order as far as possible to maintain air quality at its setpoint whilst preventing the room temperature from drifting too grea...

Page 28: ...r T56 Supply temperature sensor failure Outdoor temperature sensor failure Heat exchanger water temperature sensor failure IAQ sensor failure Relative humidity sensor failure Defrost sensor fault circ...

Page 29: ...n A maintenance alert is active The measured value is higher than the alarm threshold The measured value is lower than the alarm threshold The measured value is higher than the alarm threshold The mea...

Page 30: ......

Page 31: ......

Page 32: ...2005 Supersedes order No 15709 20 05 2004 Manufactured by Alarko Carrier Gebze Turkey Manufacturer reserves the right to change any product specification without notice Printed in the Netherlands on...

Reviews: