Special conditions:

The economiser shall be kept closed when the unit is
stopped or in unoccupied mode.

The economiser shall be held at its minimum position of
30% (this value may be configured by Carrier Service)
when:
-

the unit is in heating mode,

-

room temperature is below room control point,

-

the difference between room temperature and out-
door temperature is less than the economiser utilisa-
tion threshold (i.e. a value of 7 K which may be
configured by Carrier Service),

-

blower temperature is below 10

°

C,

-

the unit is fitted with an outside air enthalpy sensor and
this is indicating a high enthalpy which is incompatible
with feeding in air from outside,

The economiser shall be kept fully open when purge mode
is active.

The minimum position of the economiser shall be altered
in order to meet air quality requirements (see section 5.18).

The minimum position of the economiser shall not exceed
25% if the outdoor temperature is below 6

°

C.

If the outdoor temperature is below 15

°

C, all compressors

shall be stopped and only free cooling shall be authorised.

If the unit is fitted with a power exhaust louvre, this shall be
open if the position of the economiser is in excess of 50% (this
threshold may be modified by Carrier Service).

5.17 - Purge

This function can only be used if the unit is fitted with an econo-
miser. When the unit switches from unoccupied to occupied
mode, the economiser is kept fully open for two minutes pro-
vided the outdoor temperature is between 10

°

C and 21

°

C. A

purge will not be activated if the occupied period is intended to
last less than two hours. This function must be validated by the
user in the Configuration menu. It is also possible to alter the
length of the purge and the limiting outdoor temperatures in the
Setpoint menu.

5.18 - Controlling air quality

This function is used if the unit is fitted with an air quality sen-
sor and an economiser. With the aid of a PI function, it enables
the position of the economiser to be continually adjusted in
order as far as possible to maintain air quality at its setpoint
whilst preventing the room temperature from drifting too
greatly (in view of the fact that the heating or cooling stages are
not authorised to operate at this point). On the other hand if the
error in the heating or cooling room setpoint being maintained
exceeds 2.2

°

C, this function is disabled and the economiser

returns to its minimum configured position (30%), and the
heating or cooling stages are authorised to operate again. Air
quality control cannot then be authorised for another hour. This
function is not active in unoccupied mode.

5.19 - Controlling humidity

The reading from the relative humidity sensor is compared with
the humidity setpoint to check whether a humidification cycle is
needed. The humidity setpoint together with the occupied and
unoccupied period dead bands may be altered in the Setpoint menu.

The unit switches over to humidification mode if humidity is
below [humidity setpoint  less humidity dead band divided by
two]. Humidification mode stays active as long as humidity is
below humidity setpoint. The humidifier output is activated
whilst the humidification function is active. A humidifier must
be provided locally.

5.20 - Master/slave assembly

Up to 6 units can take part in a master/slave assembly. This
group then constitutes a zone in which conflicting states of
cooling/heating are not allowed between units. The master unit
determines the cooling or heating mode for the zone. If one of
the slave units is in a different cooling/heating mode from the
master unit, the unit concerned is switched to ventilation mode
without producing heat or cooling. This function is not active
in anti-freezing mode. The function operates under all
operating types. It requires the use of a communication bus
between the units concerned and must be configured by Carrier
Service.

5.21 - Fire protection

When the normally closed smoke detection contact is open, the
unit is shut down and either the fire damper is closed or the
economiser damper is opened.

Summary of Contents for PRO-DIALOG PLUS 50AZ

Page 1: ...1 50AZ UZ PRO DIALOG Control for rooftop units 50 Hz Installation operationandmaintenanceinstructions...

Page 2: ...thermostat control 23 5 2 Start stop control 24 5 3 Indoor fan on off control 24 5 4 Calculating the room temperature 25 5 5 Room temperature control point 25 5 6 Heating cooling mode 25 5 7 Anti fre...

Page 3: ...G Plus is a system for controlling rooftop air conditioners of the following types Single and dual circuit Air conditioners and reversible heat pumps PRO DIALOG Plus maintains room temperature at the...

Page 4: ...erating properly The red LED flashing for a 2 second period on the NRCP BASE board indicates correct operation A different rate indicates a board or a software failure On dual circuit units or units e...

Page 5: ...tact 1 start stop Contact 2 demand limit selection Contact 3 setpoint selection 1 Contact 4 setpoint selection 2 Connection to CCN Connector channel J3 CH24 J3 CH24 J4 CH8 J4 CH9 J4 CH10 J4 CH11a J12...

Page 6: ...a c 48 V d c max 20 V a c or V d c 3 A max 80 mA min external power supply Connector 4 pin WAGO 734 168 pitch 3 5 One per board needed 24 V a c 20 mA Connector 8 pin Wago 734 168 pitch 3 5 One per boa...

Page 7: ...fied INPUTS menu Displays the status of the unit digital and analogue inputs OUTPUTS TESTS menu Displays the status of the unit outputs and enables them to be tested CONFIGURATIONS menu Displays the u...

Page 8: ...art Stop button OPERATINGTYPES 4 DIGIT DISPLAY DESCRIPTION LOFF Local Off The unit is halted in local mode L On Local On The unit is in local control mode and is authorised to start L Sc Local On time...

Page 9: ...button again to validate the change or to access the sub menu The LED for the menu to which the item belongs as well as the two digit display then stop flashing indicating that modification mode no lo...

Page 10: ...r 2 SCHEDULE 1 SCHEduLE 1 HOLIDAYS HoLidAy HOUR DATE dAtE BROADCAST brodCASt SERVICE 1 SErviCE 1 SERVICE 2 SErviCE 2 SERVICE 3 SErviCE 3 HOLIDAYS 3 HoLidAy 3 HOLIDAYS 4 HoLidAy 4 HOLIDAYS 5 HoLidAy 5...

Page 11: ...nt room humidity unoccu pied mode Dead band room humidity unoccu pied mode Purge minimum outside temp Purge maximum outside temp Purge duration Setpoint air quality INPUTS Indoor fan status Filter add...

Page 12: ...tes left before the unit can be started This delay at start up is always active after the unit has been switched on The delay can be configured in the User Configuration 1 menu Heating cooling mode Th...

Page 13: ...ed period that has to last two hours and the outside temperature is inside the limits defined by the user Setpoint Menu the economiser is kept fully open for a configurable duration Setpoint Menu see...

Page 14: ...de outside temperature for zero offset 6 1 nnn C 4 4 60 Cooling mode outside temperature for maximum offset 7 1 n C 0 16 7 Cooling mode maximum offset value 8 1 n 10 80 Humidity setpoint occupied mode...

Page 15: ...o the compressor is switched on for 10 seconds only It is then not possible to restart the compressor for a further 30 seconds When the test is completed the following is displayed Fail displayed if t...

Page 16: ...own LOFF To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key longer than 2 seconds to activate the modification mode The password is automatically r...

Page 17: ...rotection mode selection in unoccupied mode Room temperature calculation type selection Indoor fan operation type selection Purge function selection Occupied period extension selection Smart Start fac...

Page 18: ...lection in cooling mode This is the number of compressor stages authorised for operation when the demand limit contact is closed See sections 3 5 and 5 9 9 1 0 1 2 3 4 5 5 Demand limit selection in he...

Page 19: ...FORMAT COMMENTS 0 dAtE MEnu When selected this item authorises return to the previous menu 1 n1 n2 n3 n4 Current time setting 00 00 to 23 59 n1 n2 hours 00 to 23 The first time the Enter button is co...

Page 20: ...cters in the 4 digit display flash so that hours can be adjusted n3 n4 minutes 00 to 59 Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjust...

Page 21: ...he start of daylight 1 to 1440 minutes saving time 9 nn Daylight saving stop month In this mode you enter the month in which the broadcaster will adjust its time for the end of 1 to 12 daylight saving...

Page 22: ...M100 nnn nnn nnn nnn UNITS hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 minutes minute...

Page 23: ...stage is started Single circuit reversible unit Contact G open the internal fan is stopped and the econo miser is closed Contact G closed the internal fan is activated and the economiser is opened to...

Page 24: ...marises the unit control type and stop or go status with regard to the following parameters Operating type this is selected using the start stop button on the front of the user interface Remote start...

Page 25: ...the beginning of the occupied period The control calculates an antici pated start up value in minutes based on a user configurable factor anticipated start up factor expessed in minutes degrees that m...

Page 26: ...ach compressor value weighted by the operating time This means the compressor with the least number of start ups is always the first to start up and the first to shut down 5 12 Head pressure control C...

Page 27: ...n it enables the position of the economiser to be continually adjusted in order as far as possible to maintain air quality at its setpoint whilst preventing the room temperature from drifting too grea...

Page 28: ...r T56 Supply temperature sensor failure Outdoor temperature sensor failure Heat exchanger water temperature sensor failure IAQ sensor failure Relative humidity sensor failure Defrost sensor fault circ...

Page 29: ...n A maintenance alert is active The measured value is higher than the alarm threshold The measured value is lower than the alarm threshold The measured value is higher than the alarm threshold The mea...

Page 30: ......

Page 31: ......

Page 32: ...2005 Supersedes order No 15709 20 05 2004 Manufactured by Alarko Carrier Gebze Turkey Manufacturer reserves the right to change any product specification without notice Printed in the Netherlands on...

Reviews: