4.3.11.3 - Description of the User 1 Configuration sub-menu

U

SER 1 CONFIGURATION SUB-MENU [2]

ITEM

FORMAT

UNITS

DEFAULT

COMMENTS

0

USEr MEnu

-

-

When selected this item authorises return to the previous menu.

1

«YES/no»

-

no

Control selection by thermostat

Yes = unit controlled by a thermostat
No = unit automatically controlled
This configuration permits connection of a room thermostat at the unit

2

0/1

-

0

Frost protection mode selection in unoccupied mode

1 = frost protection mode used in unoccupied mode. The unoccupied setpoint is replaced by the frost
protection setpoint.
0 = unoccupied mode operating with the unoccupied setpoint.

3[1]

0/1/2/3/4

-

0

Room temperature calculation type selection

0 = the room temperature is the medium temperature
1 = the room temperature is the maximum temperature
2 = the room temperature is the minimum temperature
3 = the room temperature is the minimum temperature in cooling mode and the maximum temperature in
heating mode
4 = the room temperature is the maximum temperature in cooling mode and the minimum temperature in
heating mode

4

0/1/2

0

Indoor fan operation type selection

0 = indoor fan permanently operating
1 = fan permanently operating in occupied mode only, fan operating intermittently in unoccupied mode
2 = fan operating intermittently in occupied and unoccupied mode

5[1]

«YES/no»

-

no

Purge function selection

YES  = purge function activated. The air in the room is renewed at the beginning of the occupied period by
opening the economiser.
No = no purging.
This item is accessible when the economiser is present.

6[1]

0/1/2/3/4

hours

0

Occupied period extension time

This is the number of hours in occupied mode generated when the extension key for the occupied period on
the room temperature sensor is activated.

7

0 to 30

-

0

Smart Start factor

Control coefficient allowing the unit to anticipate the next occupied period in order to control the room
temperature before the occupied period.

8

0/1/2

-

2

Demand limit selection in cooling mode

This is the number of compressor stages authorised for operation when the demand limit contact is closed.
See sections 3.5 and 5.9.

9[1]

0/1/2/3/4/5

-

5

Demand limit selection in heating mode

This is the number of heating stages that can operate.
0 = 0 comp 0 electric heating stage
1 = 1 comp 0 electric heating stage
2 = 2 compr 0 electric heating stage
3 = 2 compr 1 electric heating stage
4 = 2 compr 2 electric heating stages
5 = 2 compr 3 electric heating stages
See sections 3.5 and 5.9.

10[1]

0/1

-

0

Demand limit selection in defrost mode

1 = demand limit active in defrost mode. Authorises electrical demand limit in one circuit in defrost mode,
when the demand limit contact is closed.
0 = no demand limit in defrost mode. See sections 3.5 and 5.9.

11

1 to 15

min

1

Delay at start-up

. This value is reinitialised after power-up or when both circuits are halted by local, remote

or CCN command. No compressor will be started up until this pause has expired. However, the fan command
will be activated immediately.

12

«YES/no»

-

0

Cooling setpoint offset select

. See section 5.7.2.

Yes = offset selected
No = no offset

13 [1]

-5 to 21

°

C

5

Electric heating stage threshold.

 Maximum outdoor air temperature threshold for the use of electric heating

stages.

14 [1]

0 to 60

minutes

0

Electric heating stage operation schedule.

 Permits configuration of a start-up delay after unit start-up

during which the electric heater stages are not allowed to start.

15

«YES/no»

-

yes

Extended menu select

Yes = menu description available
No = menu description not available
This item authorises activating or inhibiting the menu item expanded display.

16

«YES/no»

-

no

Password for all User Configurations

Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)
No = password required for User menu only
When this item is validated, the User Password will be required for all configurations accessible by the User.

17

nn.n

-

-

Software version number

This item shows the number of the software version used by this controller. Access is read only.

Legend

1

This item shall be masked when not used.

2

Access to menu is read/write.

Summary of Contents for PRO-DIALOG PLUS 50AZ

Page 1: ...1 50AZ UZ PRO DIALOG Control for rooftop units 50 Hz Installation operationandmaintenanceinstructions...

Page 2: ...thermostat control 23 5 2 Start stop control 24 5 3 Indoor fan on off control 24 5 4 Calculating the room temperature 25 5 5 Room temperature control point 25 5 6 Heating cooling mode 25 5 7 Anti fre...

Page 3: ...G Plus is a system for controlling rooftop air conditioners of the following types Single and dual circuit Air conditioners and reversible heat pumps PRO DIALOG Plus maintains room temperature at the...

Page 4: ...erating properly The red LED flashing for a 2 second period on the NRCP BASE board indicates correct operation A different rate indicates a board or a software failure On dual circuit units or units e...

Page 5: ...tact 1 start stop Contact 2 demand limit selection Contact 3 setpoint selection 1 Contact 4 setpoint selection 2 Connection to CCN Connector channel J3 CH24 J3 CH24 J4 CH8 J4 CH9 J4 CH10 J4 CH11a J12...

Page 6: ...a c 48 V d c max 20 V a c or V d c 3 A max 80 mA min external power supply Connector 4 pin WAGO 734 168 pitch 3 5 One per board needed 24 V a c 20 mA Connector 8 pin Wago 734 168 pitch 3 5 One per boa...

Page 7: ...fied INPUTS menu Displays the status of the unit digital and analogue inputs OUTPUTS TESTS menu Displays the status of the unit outputs and enables them to be tested CONFIGURATIONS menu Displays the u...

Page 8: ...art Stop button OPERATINGTYPES 4 DIGIT DISPLAY DESCRIPTION LOFF Local Off The unit is halted in local mode L On Local On The unit is in local control mode and is authorised to start L Sc Local On time...

Page 9: ...button again to validate the change or to access the sub menu The LED for the menu to which the item belongs as well as the two digit display then stop flashing indicating that modification mode no lo...

Page 10: ...r 2 SCHEDULE 1 SCHEduLE 1 HOLIDAYS HoLidAy HOUR DATE dAtE BROADCAST brodCASt SERVICE 1 SErviCE 1 SERVICE 2 SErviCE 2 SERVICE 3 SErviCE 3 HOLIDAYS 3 HoLidAy 3 HOLIDAYS 4 HoLidAy 4 HOLIDAYS 5 HoLidAy 5...

Page 11: ...nt room humidity unoccu pied mode Dead band room humidity unoccu pied mode Purge minimum outside temp Purge maximum outside temp Purge duration Setpoint air quality INPUTS Indoor fan status Filter add...

Page 12: ...tes left before the unit can be started This delay at start up is always active after the unit has been switched on The delay can be configured in the User Configuration 1 menu Heating cooling mode Th...

Page 13: ...ed period that has to last two hours and the outside temperature is inside the limits defined by the user Setpoint Menu the economiser is kept fully open for a configurable duration Setpoint Menu see...

Page 14: ...de outside temperature for zero offset 6 1 nnn C 4 4 60 Cooling mode outside temperature for maximum offset 7 1 n C 0 16 7 Cooling mode maximum offset value 8 1 n 10 80 Humidity setpoint occupied mode...

Page 15: ...o the compressor is switched on for 10 seconds only It is then not possible to restart the compressor for a further 30 seconds When the test is completed the following is displayed Fail displayed if t...

Page 16: ...own LOFF To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key longer than 2 seconds to activate the modification mode The password is automatically r...

Page 17: ...rotection mode selection in unoccupied mode Room temperature calculation type selection Indoor fan operation type selection Purge function selection Occupied period extension selection Smart Start fac...

Page 18: ...lection in cooling mode This is the number of compressor stages authorised for operation when the demand limit contact is closed See sections 3 5 and 5 9 9 1 0 1 2 3 4 5 5 Demand limit selection in he...

Page 19: ...FORMAT COMMENTS 0 dAtE MEnu When selected this item authorises return to the previous menu 1 n1 n2 n3 n4 Current time setting 00 00 to 23 59 n1 n2 hours 00 to 23 The first time the Enter button is co...

Page 20: ...cters in the 4 digit display flash so that hours can be adjusted n3 n4 minutes 00 to 59 Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjust...

Page 21: ...he start of daylight 1 to 1440 minutes saving time 9 nn Daylight saving stop month In this mode you enter the month in which the broadcaster will adjust its time for the end of 1 to 12 daylight saving...

Page 22: ...M100 nnn nnn nnn nnn UNITS hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 minutes minute...

Page 23: ...stage is started Single circuit reversible unit Contact G open the internal fan is stopped and the econo miser is closed Contact G closed the internal fan is activated and the economiser is opened to...

Page 24: ...marises the unit control type and stop or go status with regard to the following parameters Operating type this is selected using the start stop button on the front of the user interface Remote start...

Page 25: ...the beginning of the occupied period The control calculates an antici pated start up value in minutes based on a user configurable factor anticipated start up factor expessed in minutes degrees that m...

Page 26: ...ach compressor value weighted by the operating time This means the compressor with the least number of start ups is always the first to start up and the first to shut down 5 12 Head pressure control C...

Page 27: ...n it enables the position of the economiser to be continually adjusted in order as far as possible to maintain air quality at its setpoint whilst preventing the room temperature from drifting too grea...

Page 28: ...r T56 Supply temperature sensor failure Outdoor temperature sensor failure Heat exchanger water temperature sensor failure IAQ sensor failure Relative humidity sensor failure Defrost sensor fault circ...

Page 29: ...n A maintenance alert is active The measured value is higher than the alarm threshold The measured value is lower than the alarm threshold The measured value is higher than the alarm threshold The mea...

Page 30: ......

Page 31: ......

Page 32: ...2005 Supersedes order No 15709 20 05 2004 Manufactured by Alarko Carrier Gebze Turkey Manufacturer reserves the right to change any product specification without notice Printed in the Netherlands on...

Reviews: