background image

23

5 - PRO-DIALOG PLUS CONTROL OPERATION

5.1 - External thermostat control

In appropriate cases the unit may be controlled by an external
thermostat approved by Carrier. This function requires the use
of a thermostat with volt-free contacts (contacts without
potential), as well as a specific configuration of the Pro-Dialog
control. The function is only active when operating type
Thermostat (tStA) is selected.

In this operating type, the thermostat controls the following
functions:

stopping/starting the internal fan,

determining the room temperature control point,

selecting heating/cooling,

controlling compressor capacity, gas or electric,

controlling the economiser (fully open position or
minimum closed position only).

The PRO-DIALOG Plus system continues to control the
following functions:

defrosting related to the heat pumps,

head pressure control,

power exhaust control,

minimum stop/start times on the compressors,

unit diagnostics.

The following functions are disabled:

humidification,

controlling a proportional hot water system,

timer programming,

IAQ,

demand limit,

third stage electric heater (50AZ only).

The description of the thermostat outputs, based on the unit
type, is given in sections 3.6 and 4.3.9.

Cooling only unit

Contact G open: the internal fan is stopped and the econo-
miser is closed.

Contact G closed: the internal fan is activated and the
economiser is opened to its minimum position.

Contact Y1 closed and Y2 open: if the unit is fitted with an
economiser, it is opened to its maximum position if external
conditions permit (see section 5.16). Otherwise the econo-
miser is set to its minimum position and the first compressor
is started up. If the unit has no economiser, the first
compressor is started up.

Contacts Y1 and Y2 closed: the economiser is held fully
open if external conditions are still acceptable. A compres-
sor is started up. If external conditions no longer permit
the economiser to be used, it is set to its minimum position
and the second compressor is started up. If the outdoor
temperature is lower than 15

°

C, the compressors will not be

authorised to start up and only the economiser will be used.
If the unit has no economiser, the second compressor is
started up.

Contact W1 closed and W2 open: the first gas or electric
stage is started.

Contacts W1 and W2 closed: the second gas or electric
stage is started.

Single-circuit reversible unit

Contact G open: the internal fan is stopped and the econo-
miser is closed.

Contact G closed: the internal fan is activated and the
economiser is opened to its minimum position.

Contact O closed and Y closed: if the unit is fitted with an
economiser, it is opened to its maximum position if external
conditions permit (see section 5.16). Otherwise the
economiser is set to its minimum position and the
compressor is started up in cooling mode. If the unit has no
economiser, the compressor is started up in cooling mode.

Contacts O open and Y closed: if the unit is fitted with an
economiser, it is set to its minimum position and the first
compressor is started up in heating mode.

Contact W1 closed and W2 open: the first gas or electric
stage is started.

Contacts W1 and W2 closed: the second gas or electric
stage is started.

Twin-circuit reversible unit

Contact G open: the internal fan is stopped and the econo-
miser is closed.

Contact G closed: the internal fan is activated and the
economiser is opened to its minimum position.

Contact O closed, Y1 closed and Y2 open: if the unit is
fitted with an economiser, it is opened to its maximum
position if external conditions permit (see section 5.16).
Otherwise the economiser is set to its minimum position
and the first compressor is started up in cooling mode. If the
unit has no economiser, the first compressor is started up in
cooling mode.

Contacts O, Y1 and Y2 closed: the economiser is held
fully open if external conditions are still acceptable. A
compressor is started up in cooling mode. If external
conditions no longer permit the economiser to be used, it
is set to its minimum position and the second compressor
is started up in cooling mode. If the outdoor temperature is
lower than 15

°

C, the compressors will not be authorised to

start up and only the economiser will be used. If the unit
has no economiser, the second compressor is started up in
cooling mode.

Contact O open, Y1 closed and Y2 open: if the unit is fitted
with an economiser, it is set to its minimum position and the
first compressor is started up in heating mode. If the unit has
no economiser, the first compressor is started up in heating
mode.

Contact O open, Y1 and Y2 closed: the economiser is held
in its minimum position. The second compressor is started
up in heating mode.

Contact W1 closed: the first gas or electric stage is started.

NOTE: All compressor anti-short cycles remain activated
when the unit is under the control of an external thermostat.

Summary of Contents for PRO-DIALOG PLUS 50AZ

Page 1: ...1 50AZ UZ PRO DIALOG Control for rooftop units 50 Hz Installation operationandmaintenanceinstructions...

Page 2: ...thermostat control 23 5 2 Start stop control 24 5 3 Indoor fan on off control 24 5 4 Calculating the room temperature 25 5 5 Room temperature control point 25 5 6 Heating cooling mode 25 5 7 Anti fre...

Page 3: ...G Plus is a system for controlling rooftop air conditioners of the following types Single and dual circuit Air conditioners and reversible heat pumps PRO DIALOG Plus maintains room temperature at the...

Page 4: ...erating properly The red LED flashing for a 2 second period on the NRCP BASE board indicates correct operation A different rate indicates a board or a software failure On dual circuit units or units e...

Page 5: ...tact 1 start stop Contact 2 demand limit selection Contact 3 setpoint selection 1 Contact 4 setpoint selection 2 Connection to CCN Connector channel J3 CH24 J3 CH24 J4 CH8 J4 CH9 J4 CH10 J4 CH11a J12...

Page 6: ...a c 48 V d c max 20 V a c or V d c 3 A max 80 mA min external power supply Connector 4 pin WAGO 734 168 pitch 3 5 One per board needed 24 V a c 20 mA Connector 8 pin Wago 734 168 pitch 3 5 One per boa...

Page 7: ...fied INPUTS menu Displays the status of the unit digital and analogue inputs OUTPUTS TESTS menu Displays the status of the unit outputs and enables them to be tested CONFIGURATIONS menu Displays the u...

Page 8: ...art Stop button OPERATINGTYPES 4 DIGIT DISPLAY DESCRIPTION LOFF Local Off The unit is halted in local mode L On Local On The unit is in local control mode and is authorised to start L Sc Local On time...

Page 9: ...button again to validate the change or to access the sub menu The LED for the menu to which the item belongs as well as the two digit display then stop flashing indicating that modification mode no lo...

Page 10: ...r 2 SCHEDULE 1 SCHEduLE 1 HOLIDAYS HoLidAy HOUR DATE dAtE BROADCAST brodCASt SERVICE 1 SErviCE 1 SERVICE 2 SErviCE 2 SERVICE 3 SErviCE 3 HOLIDAYS 3 HoLidAy 3 HOLIDAYS 4 HoLidAy 4 HOLIDAYS 5 HoLidAy 5...

Page 11: ...nt room humidity unoccu pied mode Dead band room humidity unoccu pied mode Purge minimum outside temp Purge maximum outside temp Purge duration Setpoint air quality INPUTS Indoor fan status Filter add...

Page 12: ...tes left before the unit can be started This delay at start up is always active after the unit has been switched on The delay can be configured in the User Configuration 1 menu Heating cooling mode Th...

Page 13: ...ed period that has to last two hours and the outside temperature is inside the limits defined by the user Setpoint Menu the economiser is kept fully open for a configurable duration Setpoint Menu see...

Page 14: ...de outside temperature for zero offset 6 1 nnn C 4 4 60 Cooling mode outside temperature for maximum offset 7 1 n C 0 16 7 Cooling mode maximum offset value 8 1 n 10 80 Humidity setpoint occupied mode...

Page 15: ...o the compressor is switched on for 10 seconds only It is then not possible to restart the compressor for a further 30 seconds When the test is completed the following is displayed Fail displayed if t...

Page 16: ...own LOFF To carry out a manual test use the arrow keys to access the output to be tested and press the Enter key longer than 2 seconds to activate the modification mode The password is automatically r...

Page 17: ...rotection mode selection in unoccupied mode Room temperature calculation type selection Indoor fan operation type selection Purge function selection Occupied period extension selection Smart Start fac...

Page 18: ...lection in cooling mode This is the number of compressor stages authorised for operation when the demand limit contact is closed See sections 3 5 and 5 9 9 1 0 1 2 3 4 5 5 Demand limit selection in he...

Page 19: ...FORMAT COMMENTS 0 dAtE MEnu When selected this item authorises return to the previous menu 1 n1 n2 n3 n4 Current time setting 00 00 to 23 59 n1 n2 hours 00 to 23 The first time the Enter button is co...

Page 20: ...cters in the 4 digit display flash so that hours can be adjusted n3 n4 minutes 00 to 59 Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjust...

Page 21: ...he start of daylight 1 to 1440 minutes saving time 9 nn Daylight saving stop month In this mode you enter the month in which the broadcaster will adjust its time for the end of 1 to 12 daylight saving...

Page 22: ...M100 nnn nnn nnn nnn UNITS hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 hrs 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 10 or 100 minutes minute...

Page 23: ...stage is started Single circuit reversible unit Contact G open the internal fan is stopped and the econo miser is closed Contact G closed the internal fan is activated and the economiser is opened to...

Page 24: ...marises the unit control type and stop or go status with regard to the following parameters Operating type this is selected using the start stop button on the front of the user interface Remote start...

Page 25: ...the beginning of the occupied period The control calculates an antici pated start up value in minutes based on a user configurable factor anticipated start up factor expessed in minutes degrees that m...

Page 26: ...ach compressor value weighted by the operating time This means the compressor with the least number of start ups is always the first to start up and the first to shut down 5 12 Head pressure control C...

Page 27: ...n it enables the position of the economiser to be continually adjusted in order as far as possible to maintain air quality at its setpoint whilst preventing the room temperature from drifting too grea...