62-61753-21
7-34
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
53
BOX TEMP OUT-OF-RANGE
TRIGGER-ON:
Alarm Only:
Condition One:
The refrigerated compartment temperature has been in range [within ±1.5°C (±2.7°F)
for perishable set points or ±1.5°C (±2.7°F) for frozen set points] at least once since the unit was
started and is now further away from set point than the limit set in the functional parameters for the
Out-of-Range Value [ 2°, 3°, or 4°C (4°, 5°, or 7°F)]
for 15 continuous minutes (30 minutes following a
defrost cycle) OR
Condition Two:
The unit is running in COOL and the Delta T (SAT minus RAT) is not greater than -
0.56°C (-1°F) for 30 continuous minutes or if the unit is running in HEAT and the SAT is not greater
than the RAT for 30 continuous minutes OR
Condition Three:
If a shutdown alarm occurs and the RAT temperature is further away from set point
than the limit set in the functional parameters for the Out-of-Range value [ 2°, 3°, or 4°C (4°, 5°, or
7°F)] for more than 30 continuous minutes regardless if the refrigerated compartment temperature
has been in-range or not.
Shut Down & Alarm:
Condition One:
When configured for shutdown the unit will shut down when the conditions for Alarm
Only Condition One are met for 45 continuous minutes.
Condition Two:
When configured for shutdown the unit will shut down when the conditions for Alarm
Only Condition Two are met for 30 continuous minutes.
UNIT CONTROL: Engine and standby operation:
If the microprocessor is not configured for shutdown, alarm only.
If the microprocessor is configured for shutdown the engine and unit will shutdown
and alarm.
RESET CONDITION: Condition 1: Auto Reset when the refrigerated compartment temperature is
within ±1.5°C (±2.7°F) of set point;
Condition 2: Auto Reset when the Delta T is greater than -0.56°C (-1°F); or
For either Condition, alarm may be manually reset via Keypad OR by turning the unit off, then back
on again.
NOTE: For Condition One, the temperature criteria for this alarm is reset, and the refrigerated compartment tem-
perature must again go In-Range before this alarm can be triggered if any of the following occur:
Pretrip is started.
Set point is changed.
A door switch or remote switch is installed and configured as a door switch, and the switch is opened indicat-
ing that the refrigerated compartment door has been opened.
NOTE: The 15, 30, or 45 minute timer is reset and starts again whenever:
The unit cycles off and restarts in Start-Stop.
The unit goes into and comes out of Defrost.
NOTE: This alarm does not go into the Inactive alarm List when it becomes inactive or is cleared.
NOTE: This alarm will not be used in Sleep Mode.
Troubleshooting steps begin on the next page.
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......