62-61753-21
5-15
CONFIGURATION
SELECTIONS
DESCRIPTION
OPTIONAL CONFIGURATIONS
(The following Configurations will display if the option has been loaded.)
OUT OF RANGE SHUTDOWN
(This Configuration is an option, it
will not display if the option is not
installed. Refer to Section 2.7.3 for
additional information.)
YES /
NO
YES = When the refrigerated compartment tempera-
ture has been out-of-range for 45 minutes, the alarm
light will come on, and the unit will shut down.
NO = When the refrigerated compartment tempera-
ture has been out-of-range for 30 minutes, the alarm
light will come on and the unit will continue to run.
COMPRESSOR ALARM
SHUTDOWN
(This Configuration is an option, it
will not display if the option is not
installed.)
YES
/ NO
If the "Compressor Alarm Shutdown" option has been
installed (refer to Unit Data List), this setting will be
available.
YES = The unit will shutdown and not restart when
alarm 13, 17, 18, 27, 28 or 56 occur 3 times within
2 hours of continuous engine operation.
NO = Normal shutdown rules for above alarms.
SET NEW HOURS
This Configuration will display when a replacement microprocessor is in-
stalled It allows entry of the hours (from the existing microprocessor) into
replacement microprocessor.
PRODUCTSHIELD SETUP
Note: ProductShield is only available when IntelliSet is installed. If installed, the following Configuration setup (
)
will be available. If the Configuration setup is not set to OFF, the sub-configurations (
) will also be available.
PRODUCTSHIELD ECONO
OFF
GO TO S/S
GO TO CONT
OFF = ProductShield Econo is OFF
GO TO START/STOP = Allows unit to be set for and
operate in Continuous Run until ambient temperature
falls
within
a user-defined range when unit will go to
Start/Stop. This allows fuel savings while offering
Continuous Run operation protection when ambient is
outside range. Unit will return to Continuous Run
when ambient goes beyond range.
GO TO CONTINUOUS = Allows unit to be set for and
operate in Start/Stop until ambient temperature falls
outside
a user-defined range when unit will go to
Continuous Run. This provides continuous air flow
and good product protection for extreme ambient
temperatures. Unit will return to Start/Stop when am-
bient comes back inside range.
The minimum range allowed for this selection is 5.5°C
(10°F).This means that the MIN temperature will nev-
er be closer to the MAX temperature than 5.5°C
ECONO MINIMUM TEMPERA-
TURE
-28.3°C to 48.3°C
(-19°F to 119°F)
in 0.5°F or °C
increments
Default:
48.3°C (119°F)
OFF
Select the lower limit of the ambient range desired for
this parameter. Refer to Section 4.6.3 for more infor-
mation on Econo Min. Temp.
ECONO MAXIMUM TEMPERA-
TURE
-28.3°C to 48.3°C
(-19°F to 119°F)
in 0.5°F or °C
increments
Default:
48.3°C (119°F)
OFF
Select the upper limit of the ambient range desired for
this parameter. Refer to Section 4.6.3 for more infor-
mation on Econo Max. Temp.
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......