62-61753-21
5-10
CONFIGURATION
SELECTIONS
DESCRIPTION
STANDBY MAXIMUM GENERATOR
AMPS
22A
10 TO 35
in 0.5A increments
Indicates to the controller the maximum allowable
amperage in Standby operation.
USE FACTORY DEFAULT SETTING ONLY, DO
NOT OPERATE UNIT WITH DIFFERENT SETTING.
STARTUP MAXIMUM GENERATOR
AMPS
17A
10 TO 35
in 0.5A increments
Indicates to the controller the maximum allowable
amperage during start up.
USE FACTORY DEFAULT SETTING ONLY, DO
NOT OPERATE UNIT WITH DIFFERENT SETTING.
DIESEL OFFSET MAXIMUM AMPS
4.0A
0 TO 10
in 0.5A increments
Indicates to the controller the maximum allowable
amperage in low speed operation.
USE FACTORY DEFAULT SETTING ONLY, DO
NOT OPERATE UNIT WITH DIFFERENT SETTING.
STANDBY STARTUP DELAY
OFF
5 Seconds
10 Seconds
15 Seconds
20 Seconds
Indicates to the controller the delay for this unit when
starting in standby.
This setting is used when multiple units are on the
same line to stagger the occurrence of high inrush
current in situations such as restart after a power
loss.
DISPLAY TOTAL ENGINE HR
YES
/ NO
YES = This hour meter will be displayed during the
startup messaging sequence and will be in hour me-
ter menu.
NO = This hour meter will not be displayed during the
startup messaging sequence and will be shown with
the "other meters and counters".
DISPLAY STANDBY RUN HR
YES
/ NO
YES = This hour meter will be displayed during the
startup messaging sequence and will be in hour me-
ter menu.
NO = This hour meter will not be displayed during the
startup messaging sequence and will be shown with
the "other meters and counters".
DISPLAY TOTAL SWITCH ON HR
YES
/ NO
YES = This hour meter will be displayed during the
startup messaging sequence and will be in hour me-
ter menu.
NO = This hour meter will not be displayed during the
startup messaging sequence and will be shown with
the "other meters and counters".
DIESEL RESET VALUE
(Refer to Section 8.2 for oil/filter
change intervals.)
0
50 TO 30,000
hours in 50 hour
increments
When the meter is reset, the value selected here will
be added to the to the present meter reading to indi-
cate to the controller when the next service interval
alarm will be triggered. If the value entered is "0" the
alarm feature is turned off.
STANDBY RESET VALUE
0
50 TO 30,000
hours in 50 hour
increments
When the meter is reset, the value selected here will
be added to the to the present meter reading to indi-
cate to the controller when the next service interval
alarm will be triggered. If the value entered is "0" the
alarm feature is turned off.
SWITCH ON RESET VALUE
OFF
50 TO 30,000
hours in 50 hour
increments
When the meter is reset, the value selected here will
be added to the to the present meter reading to indi-
cate to the controller when the next service interval
alarm will be triggered. If the value entered is "0" the
alarm feature is turned off.
Summary of Contents for NDK33BN0KB
Page 2: ......
Page 3: ...OPERATION SERVICE MANUAL for VECTOR 1550 1550 CITY Trailer Refrigeration Units...
Page 4: ......
Page 14: ......
Page 22: ...62 61753 21 1 8 1 5 SAFETY DECALS 62 61343 00 Rev or 62 02139 01 Rev C 62 02143 00 Rev...
Page 24: ...62 61753 21 1 10 62 60192 00 Rev D...
Page 30: ...62 61753 21 2 6...
Page 48: ......
Page 212: ......
Page 226: ......
Page 248: ......
Page 252: ......
Page 262: ......
Page 270: ......